Manual Volume Control Damper 300 x 300 mm
- A locking quadrant retains the balancing position.
- Formed blade ribs resist flexing across the compact opening.
Set a fixed restriction in a compact branch
The 300 × 300 mm manual damper uses linked galvanized 3V blades and a lockable quadrant to balance a small rectangular duct. The installer measures branch flow, adjusts the blade angle and locks the setting. The formed blade ribs provide stiffness; they do not define a certified pressure limit or a shut-off leakage class.
A retained angle is not a retained airflow
After adjustment, the damper remains at the selected angle. If fan pressure or another branch changes, its airflow can change even though the handle has not moved. Use it for a stable design duty with periodic balancing, and consider a regulating device where maintaining flow through changing pressure is necessary.
| Reference feature | Specification detail |
|---|---|
| 300 × 300 mm nominal opening | Identify whether the drawing dimension refers to the duct opening, frame or flange; allow the required installation clearance. |
| Multiple linked 3V blades | State blade action, airflow direction where relevant and performance at the selected opening. |
| Manual locking quadrant | Choose the operating side and clearance beyond insulation or the ceiling. |
Angle marks are position references, not calibrated flow readings. A nearly closed setting can create turbulence and noise close to a terminal. Review pressure drop at the required volume using data for the selected blade and frame assembly. Leakage and structural capability require data for the supplied size and construction.
Install without restricting blade travel
Keep the frame square and support the duct so its connection does not twist the damper. Locate screws away from blades and concealed linkage. An extended shaft can bring the quadrant beyond insulation, but it must be supported and connected according to the approved arrangement.
Balance with filters, terminals and normal operating controls in their intended state. Record measured flow and handle position, tighten the locking mechanism and check that locking has not moved the setting. Revisit the balance after branch alterations. During inspection, look for loose linkage, binding blades and a slipping clamp.
Quotation and acceptance
Specify dimensions, pressure duty, blade action, quadrant side, flanges and shaft extension. Require smooth travel and retention of the agreed setting, plus measured branch flow at the commissioning condition. A balancing damper is not a fire/smoke damper or a positive isolation barrier.