Linear Slot Air Diffuser One-Slot 15 x 1200 mm
- Single slim opening minimizes visible ceiling width.
- Adjustable blade setting changes the local discharge direction.
A narrow architectural supply line
The one-slot diffuser uses a 15 mm passage along a nominal 1200 mm extruded aluminum section. It suits a ceiling or perimeter detail where a narrow visible opening is desirable. Manually adjustable blades set the discharge direction for the selected room duty; the slot provides distribution, while a matching plenum supplies air along its length.
Visible length and active length
A continuous ceiling line can contain several active sections and blank sections. Only the supplied active length contributes to the specified air duty. End caps, joins and inactive pieces must be shown on the layout rather than counted automatically as discharge length. The nominal 1200 mm section also needs an approved end-to-end and opening dimension for fabrication.
| Catalog item | Selection detail |
|---|---|
| Slots | One, 15 mm nominal width. |
| Section | 1200 mm nominal length. |
| Body | Extruded aluminum; white coating option. |
| Pattern | Manual horizontal or downward adjustment. |
| Accessories | Matching plenum, end caps and continuous-run joining sections. |
Select airflow per active length
Evaluate flow per active metre with the selected slot geometry, plenum and pattern setting. A very narrow opening can become noisy or require excessive pressure if it is used to carry too much air. Longer active length, more outlets or a wider/multiple-slot arrangement may be preferable to simply increasing velocity.
A horizontal ceiling jet depends on its installation relative to the ceiling and on supply temperature. Downward discharge can create drafts if selected without considering throw and occupied height. The same setting should not be assumed suitable for both cooling and heating conditions. Pattern control may also change resistance, so recheck the volume after adjustment.
Installation and maintenance
Support the plenum separately from the visible rails and keep the long section straight. Alignment pieces join the visible run; they do not replace sealed duct connections between boxes. Provide access to each balancing point and avoid an inlet arrangement that feeds only one end unevenly. Coordinate perimeter insulation and vapour sealing where cold air passes through a humid ceiling void.
Clean the narrow passage without bending the blades or filling it with paint. Record controller positions before access work and restore them afterward. A quotation should identify active and blank lengths, end treatment, border, plenums, insulation, connections and balancing hardware. Acceptance should cover flow by section, pattern setting, straightness, secure fixing and the agreed room air-motion and acoustic checks.
Planning your Linear Slot Air Diffuser One-Slot 15 x 1200 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.