Interlocked Cleanroom Door Steel Swing with Integrated Interlock
- Visible status indication helps users recognize when passage is available.
- A single moving leaf keeps the locking interface localized.
- The assembly can communicate with a coordinated group of other doors.
A complete swing door for sequential access
This doorset combines a galvanized-steel-faced leaf, hollow-chamber cleanroom frame and integrated lock, contact and red/green indication. It suits personnel routes where there is enough swing clearance and the opening belongs to a group of doors that must operate in sequence. The interlock controls permission to open; it does not itself establish room cleanliness or pressure recovery.
Define what each status means
A normal sequence receives an access request, checks the associated doors, releases the permitted opening and prevents conflicting release until the passage is complete. The closed-position contact reports leaf position. If the process also needs proof of lock engagement, that is a separate input. Red and green meanings should follow the approved sequence so the display does not show “available” while another condition still prevents passage.
Magnetic locks and electric strikes have different mounting and mechanical interfaces. Their power-loss behavior and emergency release must be chosen explicitly for the route. The 24 V DC specification applies to the interlock hardware; supply capacity must include the controller, locks, indicators and accessories, allowing for cable voltage drop.
Door, wall and control interfaces
Provide reinforcement for hinges and locking components and a cable route that can be serviced without damaging the sealed partition. The door must close reliably under room pressure before the position signal changes. A magnet positioned to signal too early can allow the next door to release while a gap remains.
A timed delay can organize access, but does not measure pressure or purge completion. Where those conditions govern release, include the appropriate process inputs and acceptance logic. Define which events are sent through the optional building-management interface and keep emergency operation available under the specified failure conditions.
Quotation and acceptance
Include leaf and frame, closer arrangement, lock, contact, indicators, emergency release, controller allocation, power supply, cabling and commissioning responsibilities. Test both normal directions, simultaneous requests, a held-open door, contact fault, power loss and emergency release, followed by controlled reset. Service should check alignment, latch or magnet engagement, cable condition and the displayed state against actual operation. Do not treat a green lamp as evidence of a validated room condition.
Planning your Interlocked Cleanroom Door Steel Swing with Integrated Interlock specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.