Interlocked Cleanroom Door 1350 mm Unequal-Leaf HPL

An unequal HPL pair combines everyday active-leaf access with monitored secondary-leaf release for larger transfers.
  • Routine passage can use only the larger leaf.
  • A secondary leaf gives extra transfer width when needed.
  • The HPL faces maintain a nonmetallic finish across the pair.
Request a Quote Browse Products

Routine passage through the active leaf

This unequal HPL pair uses the larger leaf for everyday personnel access and the smaller leaf for occasional wider transfers. The 1350 × 2100 mm dimensions describe the wall hole. Finished clear passage depends on the frame, leaf division, hardware and opening angle. The active-leaf width and total usable equipment opening should both be shown on the approved drawing.

The secondary leaf belongs in the interlock logic

Monitoring only the active leaf can leave an unrecognized opening when the secondary leaf is released. Include both leaves in the boundary status whenever either can open. If the process needs proof that the smaller leaf is secured, provide the corresponding restraint or lock feedback instead of assuming its position contact proves engagement.

Define how a wider-transfer request is made, which other doors remain inhibited and how the system returns to normal operation. A temporary mechanical release must not silently bypass the access sequence. Emergency release and reset should follow the site's escape requirements and preserve a clear distinction between normal permission and override.

Frame and closing-hardware choices

The frame options suit 50 or 100 mm cleanroom panel walls. These are wall thicknesses, not leaf thicknesses. Hinges, lock fixings and any concealed closer need reinforcement within the selected frame and leaf. Exposed closers are easier to access; concealed units reduce projections but require compatible internal space and a planned service route.

Where an overlap requires a particular closing order, coordinate the two leaves so each can seat and latch properly. Room pressure and seals add operating resistance. Do not compensate for rubbing at the center by increasing closer force without correcting alignment. Clean HPL edges and hardware joints with compatible agents and keep secondary-leaf receivers clear of debris.

Quotation and acceptance

Include leaf split, wall and frame details, closers, locks, contacts for both leaves, indicators, override controls, supply and field wiring. Commission routine active-leaf use, full-width transfers, simultaneous requests, secondary-leaf-open conditions, fault handling and emergency reset. A closed pair and a timed delay do not prove pressure or purge recovery; add measured process conditions only where the control specification requires them.