Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Cleanroom Doors, Windows & Interlocks / Insulated High-Speed Roll-Up Door 1300 g/m2 Polyfoam Cleanroom
zhengfeng-INSULATED-HIGH-SPEED-ROLL-UP-DOOR-POLYFOAM-1300

Insulated High-Speed Roll-Up Door 1300 g/m2 Polyfoam Cleanroom

An opaque insulated polyfoam curtain provides a rolling barrier between conditioned areas with continuous side seals.
  • Insulated polyfoam distinguishes the curtain from standard thin PVC.
  • Continuous side sealing accompanies the flexible roll-up barrier.
  • The solid curtain screens activity across the opening.
Request a Quote Browse Products

An insulated flexible barrier between conditioned rooms

The 1300 g/m² polyfoam curtain provides an insulated alternative to a thin uninsulated fabric sheet while retaining vertical roll-up storage. It suits frequently used transitions between differently conditioned support or production areas. The opaque surface provides privacy; its lack of a view through the door makes traffic detection and approach layout particularly relevant.

Separate curtain mass from thermal performance

The 1300 g/m² value describes areal mass. It does not provide a U-value, R-value or permitted temperature difference. Thermal selection needs the finished curtain construction and the complete-door performance, including seals, header and side columns. During frequent traffic, the time spent open and the air exchanged through the passage can outweigh heat conducted through the closed curtain.

The reference size envelope is up to 4000 mm wide and 4000 mm high. The heavier curtain changes moving load and roll geometry, so drive settings and header space should be selected with this curtain fitted. An insulated sheet should not be treated as a drop-in replacement for any existing rapid-door drive.

Sealing, condensation and cleaning

Continuous side seals and a soft bottom reduce gaps around the flexible panel. They require aligned guides and a suitable floor contact surface. The 304 stainless housing and slanted control enclosure remain potential cold surfaces; condensation depends on local surface temperature and the humidity of the warmer side. State conditions on both sides of the opening when selecting materials, electrical protection and any condensation-control measures.

Keep the foam covering intact. Tears, separating layers or damaged edges can compromise cleanability and thermal consistency. Clean with agents compatible with the curtain covering and joints, and allow appropriate drying before prolonged closure. Avoid interpreting the heavier construction as proof of suitability for subzero service.

Quotation and performance checks

Specify clear dimensions, both room conditions, cycle rate, traffic, compatible curtain finish, controls and touchless activation if required. Include guides, seals, structural fixing, installation and a replacement-curtain scope. Handover should demonstrate smooth rolling without creasing, safety detection, complete closure and the specified power-loss procedure. Any thermal or air-leakage target should be supported by evidence identifying the tested configuration and conditions.

Planning your Insulated High-Speed Roll-Up Door 1300 g/m2 Polyfoam Cleanroom specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.