Insulated Duct Access Door 200 x 200 mm
- A retained hinged leaf avoids handling a loose cover overhead.
- The small opening minimizes the area interrupted in the duct wall.
A small hinged opening for a reachable service point
The 200 x 200 mm insulated access door is intended for a local inspection or hand task in the flat wall of a rectangular duct. The galvanized hinged leaf holds a 25 mm glass-wool layer and closes against a rubber perimeter seal with two clasps. The hinge retains the cover while the service point is accessed.
Select for the task behind the opening
A nominal 200 mm square is not necessarily the clear aperture after the frame and hinge are fitted. Check hand reach, tool length, viewing angle and the distance to the sensor or damper. An inspection opening that permits a view may still be too small to remove a component.
| Item | Catalog reference |
|---|---|
| Nominal access size | 200 x 200 mm. |
| Door/frame | Galvanized steel, hinged. |
| Insulation | 25 mm glass wool. |
| Closure | Two clasp locks with rubber perimeter seal. |
| Surface | Flat rectangular duct wall. |
| Options | Hinge orientation and frame attachment detail. |
Use the actual cut-out and fixing template, avoiding reinforcing ribs, seams and moving components. The frame-to-duct joint and door-to-frame seal are two separate leakage paths. A flat frame should not be forced onto a round duct; a matching curved access assembly is needed for that surface.
Thermal continuity and service access
The insulated leaf restores part of the thermal layer, but the frame, hinge and cut insulation edge can remain thermal bridges. Coordinate the surrounding duct insulation and vapour seal while keeping the door operable. Protect the glass-wool edges and inner surface so the air stream and cleaning procedure do not disturb fibres.
Leave external swing and clasp clearance after ceiling installation. Isolate the equipment and relieve duct pressure before opening. The hinge supports the retained leaf but is not a tool support or an indication that opening against pressure is safe.
Quotation and acceptance
Specify clear aperture, duct wall thickness, hinge direction, pressure duty, temperature and gasket compatibility. Include frame fixings, sealant and insulation finishing in the scope. Acceptance should verify useful reach, secure latch compression and leakage at the agreed duty. After maintenance, inspect the gasket for dirt or damage and close both clasps. Insulation thickness alone provides neither a whole-door thermal rating nor fire resistance.
Planning your Insulated Duct Access Door 200 x 200 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.