Home / Products / Air Ducts & Air Distribution / Instrument Test Port for Air Duct 1-Inch Insulated
zhengfeng-INSTRUMENT-TEST-PORT-AIR-DUCT-1IN-INSULATION

Instrument Test Port for Air Duct 1-Inch Insulated

A raised cam-operated fitting provides repeatable probe entry through a nominal one-inch insulation layer, with the measurement layout defined separately.
  • The raised neck keeps the access point reachable above insulation.
  • A reusable locking plug supports repeated commissioning visits.
Request a Quote Browse Products

Reusable probe access through a one-inch insulation build

The raised test fitting brings a removable cam-operated plug above the duct insulation, avoiding a new drilled and taped hole at each measurement visit. Its cast zinc-alloy body, zinc-plated cap and expanding neoprene plug provide a reusable access point for an appropriate probe.

Fit the instrument as well as the insulation

ItemCatalog reference
Insulation accommodation1 inch (25.4 mm) nominal.
Internal bore1-1/16 inch.
Body/capCast zinc alloy and zinc-plated steel.
ClosureCam-action expanding neoprene plug.
Base sealFlat neoprene gasket.

The bore must pass the complete sensing head or bent probe, not merely its stem. Include the raised neck in insertion-depth calculations so the sensing point reaches the planned position inside the duct. The actual insulation jacket and external clearance must still allow the cam lever to operate.

A measurement opening is not a measurement method

The fitting can provide access for a pitot or temperature probe, but it does not establish a valid airflow reading. A duct traverse requires suitable measurement locations and multiple points across the flow section; one centre reading is not generally the average velocity. Locate enough ports to reach the prescribed points and allow room outside to insert and rotate the instrument.

A large open probe bore is also not a static-pressure tap by itself. Use the proper static probe or dedicated pressure fitting and its specified orientation. Air leaking around an inserted probe can affect conditions, so the measurement procedure should address the temporary opening.

Installation and service

Seal the body to the duct separately from the removable plug. Protect the insulation edge and reinstate the vapour barrier around the neck without blocking the closure. Choose gasket and plug material against the actual temperature, pressure and chemical exposure; a temperature rating for a similar port does not establish this assembly's limit.

During repeated access, inspect the neoprene for cracking or compression damage and keep the bore clean. Close the cam to its intended engagement without forcing it to compensate for an incorrect or worn plug.

Quotation and acceptance

Specify insulation build, duct surface, probe geometry, port layout, operating duty and sealing materials. Include mounting fasteners, compatible sealant and replacement plugs. Acceptance should demonstrate full probe reach, accessible operation and leak-tight closure at the agreed condition. Record measurement positions so future balancing visits use the same traverse geometry.

Planning your Instrument Test Port for Air Duct 1-Inch Insulated specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team