Home / Products / Air Ducts & Air Distribution / HVAC Damper Actuator 10 Nm 24 V Spring-Return
zhengfeng-HVAC-DAMPER-ACTUATOR-10NM-SPRING

HVAC Damper Actuator 10 Nm 24 V Spring-Return

A modulating drive stores mechanical spring energy for a defined return movement after power removal, with final blade position set by installation.
  • The stored spring energy provides a defined power-loss movement.
  • Manual crank operation supports local adjustment without a live drive command.
Request a Quote Browse Products

Modulating operation with stored mechanical return energy

The nominal 10 Nm, 24 V spring-return actuator uses a 2–10 V DC input for normal positioning. Powered movement stores energy in a spring, which moves the shaft toward its defined return position when supply power is removed. The deeper spring housing and manual-crank access must be considered when locating the drive.

Choose the safe position at the damper

Clockwise or counterclockwise actuator return does not by itself mean fail-open or fail-closed. Shaft orientation, linkage and blade mounting establish the final damper position. Define that position in the ventilation sequence and demonstrate it on the assembled unit.

Loss of command while power remains available is different from loss of supply power. The input circuit and configuration determine the first response; the spring determines the second. Both conditions should be included in commissioning where the system depends on them.

ItemSelection basis
Nominal torque10 Nm class; verify both powered and spring-return capability for the actual load.
Supply/command24 V AC/DC and 2–10 V DC modulation.
ReturnMechanical spring with installation-specific direction.
Manual operationCrank facility, using the selected model's release and locking procedure.
Required dataPowered time, fail-return time versus temperature/load, travel and electrical sizing.

Return speed is conditional

A less-than-20-second return cannot be assumed across all temperatures, loads and models. The actual time must meet the system requirement under its specified conditions. Likewise, powered stroke time and spring-return time are separate values. Use the supplied datasheet rather than combining values from different drives.

Mount the shaft clamp and anti-rotation restraint so the spring can move the damper freely. Check the blade seat and linkage for binding at the return endpoint. Manual locking or crank operation can change the available return function, so restore normal operation according to the instructions before handover.

Quotation, maintenance and acceptance

Specify return direction, torque in both modes, shaft dimensions, travel, ambient conditions, timing, electrical lead and any feedback. Price mounting fittings and required accessories with the drive. During service, isolate power and manage stored spring energy using the manufacturer's procedure.

Acceptance should confirm analog travel, actual final blade position and return after power removal at the required test condition. Inspect coupling slip or binding if timing changes. Spring return alone does not qualify an ordinary HVAC actuator for fire/smoke service; that use requires an approved complete assembly.