Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / HVAC Damper Actuator 10 Nm 24 V Modulating
zhengfeng-HVAC-DAMPER-ACTUATOR-10NM-MODULATING

HVAC Damper Actuator 10 Nm 24 V Modulating

An analog-command rotary drive for intermediate damper positioning where a mechanical power-loss return function is not required.
  • Analog input supports intermediate blade positions.
  • A manual release permits local shaft adjustment.
Request a Quote Browse Products

Analog position control without a power-loss return mechanism

The nominal 10 Nm, 24 V actuator clamps to a damper shaft and uses a 2–10 V DC command to set an intermediate angular position. Its non-fail-safe construction is intended for a control sequence that does not require a spring-driven position after power loss. The manual release allows local alignment using the selected drive's instructions.

Position is not airflow

A mid-range voltage requests a mid-range position within the configured travel; it does not guarantee half of the design airflow. Damper flow depends on its geometry and system pressure. For actual airflow or room-pressure regulation, a controller and appropriate measurement provide the feedback around this positioning device.

ItemSelection basis
Torque class10 Nm nominal; size against the actual damper load and required allowance.
Supply24 V AC/DC, with electrical sizing from the selected model.
Command2–10 V DC modulating, with direction and travel configured.
Failure functionNon-fail-safe; loss-of-signal and loss-of-power behaviour require separate definition.
InterfacesShaft clamp, manual release and mounting/lead accessories.

Travel and timing must match the control loop

The catalog's 150-second-per-90-degree timing is a configuration target that needs confirmation for the delivered model. It should not be assumed programmable merely because another actuator offers adjustable timing. Select a stroke time compatible with the controller tuning; slow movement can limit response, while rapid repeated corrections can cause hunting in a poorly tuned loop.

Match the shaft diameter/profile, clamp engagement and anti-rotation bracket. Set mechanical stops so the damper closes correctly without overdriving its seals. Keep the manual release accessible and ensure it is re-engaged after adjustment.

Electrical and service checks

Coordinate signal reference, polarity, input impedance and cable routing with the controller diagram. A feedback output or auxiliary switch is a separate feature and must be ordered if required. Transformer and cable selection use the manufacturer's sizing data, not only a nominal running-watt figure.

The quote should identify exact model, torque, timing, command range, shaft fittings, wiring and optional feedback. Acceptance should compare commands with actual travel at several points and test signal interruption and power loss separately. Record the final end stops and direction. This general HVAC actuator is not automatically suitable for a certified fire/smoke damper assembly.

Planning your HVAC Damper Actuator 10 Nm 24 V Modulating specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us