H-Type Cleanroom Panel Connecting Profile 100 mm Slot Receiver
- Nominal 100 mm slots require finished clearance matched to the panel.
- A shared joining member keeps adjacent edges on one joint line.
A double-sided receiver for thick panel edges
This aluminum H-section provides opposing nominal 100 mm receiving slots for a vertical cleanroom wall joint. Each panel enters a channel on one side of the central web. The joint locates the adjoining edges and covers their ends while leaving the retention and sealing arrangements to the coordinated wall detail.
Allow for the real panel thickness
A nominal 100 mm panel cannot be assumed to fit a nominal 100 mm opening without clearance. Use the finished panel dimensions after temporary protective films have been removed. Include manufacturing variation, permanent coatings and any gasket or adhesive layer in the fit calculation. Specify the finished clear opening rather than relying only on nominal labels.
Engagement depth and flange stiffness matter as well as slot width. A shallow overlap can expose an edge when the panel moves; forcing a thick panel into a tight channel can spread the flanges or mark its skins. Increasing the slot width indiscriminately may instead leave a loose, difficult-to-seal joint.
Coordinate retention and joint continuity
Establish how the receiver is supported at the head and base and whether additional fixings retain the panels. The H-bar is not automatically a structural post. Pressure or equipment loads need a defined route through the wall supports.
Plan the insertion order before closing adjoining bays. Seal the designated panel-to-profile interfaces and the ends of the vertical joint. Where opposite rooms have different thermal conditions, assess the continuous metal path through the connection rather than assigning it the insulation value of the panel core.
Purchasing and inspection
Send the panel build-up, finished thickness range, receiver drawing, wall height and sealing proposal. Quote anodized or powder-coated finish, cut lengths, machining, fasteners and seals as selected items. Accept by measuring both finished slots and trial-fitting representative panels, then checking alignment, engagement and continuous seals. Maintenance should investigate loose panels or repeated seal opening at the connection rather than treating every failure as a sealant-only problem.
Planning your H-Type Cleanroom Panel Connecting Profile 100 mm Slot Receiver specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.