Galvanized Steel Rectangular Air Duct 600 x 300 mm
- Broad airway accommodates grouped terminal feeds.
- Rectangular geometry uses ceiling width efficiently.
- Clamped seal mouldings remain accessible at section joints.
A wider branch for several terminal connections
The 600 × 300 mm rectangular duct provides a nominal 0.180 m² internal area with a 2:1 aspect ratio. It can distribute air to a group of terminals while using available ceiling width. The section has three times the area of a 300 × 200 mm branch, but system resistance, fittings and fan capability determine the usable airflow.
Size for the operating combination
The common duct carries the combined demand of connected outlets. Establish simultaneous flow and any reduced-use modes before locating take-offs and balancing dampers. A restricted take-off can starve one terminal even when the main branch is large enough. Increasing fan pressure may then create excess flow or noise at other outlets.
Coordinate take-off spacing, transitions and access openings with the wall construction. Multiple nearby cutouts reduce the remaining panel stiffness. End flanges stabilize the perimeter, but they do not necessarily support every part of a broad flat wall between joints.
Specify strength and leakage separately
| Requirement | What the offer should identify |
|---|---|
| Material | Sheet thickness, Z275 coating requirement and material evidence. |
| Pressure duty | Positive or negative design conditions and reinforcement arrangement. |
| Leakage acceptance | Named method or standard, limit, test pressure and test scope. |
| Joint system | Profile, corner pieces, gasket and mechanical fastening. |
An airtightness class must refer to its governing test method. It should not be confused with a similarly named seal class that describes where sealant is applied. A label alone does not prove the assembled branch meets its leakage requirement.
Include fittings, access doors, supports, insulation and site jointing in the quotation. Maintain space to reach clamps and balancing devices after surrounding services are installed. Acceptance should combine construction and joint checks with the specified leakage test and terminal balancing. During maintenance, investigate loose supports, damp insulation and changes in outlet flow; sealing one visible flange cannot resolve every distribution problem.
Planning your Galvanized Steel Rectangular Air Duct 600 x 300 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.