Fire-Rated Rock Wool Cleanroom Panel 100 mm Steel-Framed Fire-Resistant
- Deep mineral section is supplied as one component.
- Galvanized edge members retain the panel perimeter.
A deep framed rock-wool boundary requiring assembly evidence
This 100 mm module uses rock wool, metal skins and a galvanized perimeter completed by separate corner elements. It is intended for substantial cleanroom partitions. When a fire-rated boundary is required, the exact panel, supports, joints and openings must form an evidence-backed assembly.
Depth does not assign a fire-resistance period
A thicker mineral section may change heat transfer and structural behaviour, but a time rating cannot be calculated simply by scaling from a thinner panel. Fire tests evaluate a defined element under a specified exposure and performance criteria. Required evidence must address the installed orientation, permitted dimensions, restraint and construction, including any relevant loading.
The wall also needs a normal structural design for pressure, self-weight and attached components. Fire-resistance evidence and an ambient-temperature load assessment serve different purposes. Available panel production length does not establish either allowable unsupported height or an accepted fire-test field of application.
Coordinate deep frames and perimeter protection
Reference construction includes 0.5–1.0 mm faces, 0.8 mm galvanized frame members and 1.0 mm corner stock. Module-width choices are 980, 1160, 1180 or 1200 mm subject to the selected connection. Specify the actual metal sections and fixings. Corner stock closes the frame junction; it is not independent proof of a fire rating.
Aluminum connectors and continuous edges need matching evidence for their seal and attachment details. Door throats, glazed openings and service sleeves must fit the deep wall and preserve its required protection. Head-of-wall movement should be accommodated by an appropriate joint detail instead of rigidly sealing a gap that is expected to move.
Procurement, acceptance and later changes
Quotation should include the required classification, approved construction record, panel layout, structural supports, protected openings, perimeter joints and inspection scope. Identify whether any overhead application is proposed, since wall evidence does not automatically establish ceiling performance or walkability.
Acceptance should verify supplied materials and dimensions, inspect concealed fixings and compare the finished boundary with the documented assembly. Keep photographs and identification of protected service penetrations for maintenance. After an impact, leak or equipment relocation, inspect both the visible damage and affected core, frame and seals. Restoring a smooth surface alone may leave the required fire boundary incomplete.
Planning your Fire-Rated Rock Wool Cleanroom Panel 100 mm Steel-Framed Fire-Resistant specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.