Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Explosion Relief Damper 250 x 750 mm Self-Closing
zhengfeng-EXPLOSION-RELIEF-DAMPER-250X750

Explosion Relief Damper 250 x 750 mm Self-Closing

A medium lamella array with optional movement monitoring and suction-point integration, selected as part of the complete machine protection system.
  • The medium footprint balances available enclosure area and relief opening size.
  • A proximity-switch option provides a separate indication of opening.
Request a Quote Browse Products

A monitored relief array beside an extraction interface

The 250 x 750 mm configuration uses multiple short aluminum leaves in a rectangular machine-enclosure opening. A nominal 100 mm leaf height and 87-degree stop describe its short-travel, gravity-return arrangement. Its optional proximity switch and integrated suction connection make the local interface a central part of the selection.

Extraction and relief have different operating duties

Normal extraction removes air or mist through a ducted route. Explosion relief must respond to a rapid pressure rise through a validated discharge path. Combining their mounting positions does not make an ordinary extraction duct a safe explosion discharge route. Connected equipment and ducts may require additional protection or isolation specified by the machine protection design.

The footprint is not the effective vent area. Leaves, frame obstructions, opening dynamics and any downstream restriction affect performance. The required selection depends on the process hazard, enclosure volume and strength, activation conditions and permitted reduced pressure.

ItemReference arrangement
Nominal format250 x 750 mm.
LamellasLightweight aluminum, nominal 100 mm height.
Travel stop87 degrees in the catalog design.
Return actionGravity, with orientation and condition checked for the actual assembly.
OptionsProximity monitoring, integrated suction point and mounting flanges.

What the opening signal can prove

A proximity switch can register movement at its sensing point. It does not prove every lamella opened, establish vent capacity or detect all hazardous combustion events. Specify the contact or electronic interface, sensing location, power-loss response and machine shutdown logic for the intended monitoring function.

Access for cleaning matters near oil-mist extraction. Deposits can increase friction and obstruct the sensing target. The switch and wiring must not intrude into the flap path or constrain the moving leaves.

Installation and return to service

Support the frame without distortion, leave the complete opening sweep free and assess the hot-gas/material discharge zone separately from the mechanical clearance. Any protective duct, guard or added flame-control component must be included in the qualified arrangement.

The quotation should identify the enclosure interface, relief evidence, suction connection, switch and controls, mounting parts and inspection procedure. Acceptance includes documentation for the actual hazard and device, installation checks and a functional monitoring test. A closed flap after an event is only a mechanical state; restart requires the specified machine and protection-system review.

Planning your Explosion Relief Damper 250 x 750 mm Self-Closing specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us