Dynamic Fire Damper 914 x 914 mm Horizontal
- Large format serves substantial vertical duct penetrations through floors.
- The horizontal closure mechanism supports curtain travel across the opening.
A spring-driven curtain in a floor plane
The 914 x 914 mm horizontal configuration is intended for a duct penetration through a floor or other specifically approved horizontal barrier. Its folding curtain moves across the opening under its closing mechanism. Unlike a vertical wall-plane assembly, gravity does not act along the same curtain travel path.
A wall damper cannot be turned flat and assumed suitable. Approval must cover horizontal installation, this opening size, the actual floor construction and dynamic duty. The product's square dimensions and spring material do not establish a fire rating.
Reference geometry and installation requirements
| Item | Catalog reference |
|---|---|
| Nominal size | 914 x 914 mm. |
| Plane | Horizontal. |
| Frame/curtain | Galvanized steel with folding curtain. |
| Closing spring | Stainless steel construction. |
| Frame depth | 56 mm reference; complete sleeve depth and blade envelope require the approved drawing. |
| Thermal release | Temperature and part number specified within the approved assembly. |
Floor opening, supports and access
Coordinate the sleeve, supporting and retaining components, required expansion clearance and duct connection with the floor detail. The relatively wide opening needs a square, undistorted frame so the curtain can travel. Duct weight and movement must not be transferred in a way that compromises the listed installation.
Above-floor access alone may not make the thermal link or curtain mechanism reachable. Draw the inspection and reset route before locating equipment, ceiling tiles and pipework around the penetration. Keep spring and blade travel free of debris and screws. Any closure test must use the manufacturer's controlled procedure.
Choose ratings separately from link temperature
A thermal link initiates closure at its specified response condition; it does not supply the assembly's fire-resistance duration. Higher-temperature links and a different sleeve cannot be fitted on the assumption that the original qualification remains valid. Likewise, dynamic flow and pressure limits must come from the approved horizontal configuration rather than a wall-mounted model.
Request the model identification, horizontal approval, required fire classification and dynamic limits along with the proposed floor construction. Quote the connecting sleeve, retaining/support components, permitted link and service access. Acceptance includes documents, orientation and installation checks plus functional operation and a maintenance record. A fire damper must have separate smoke-leakage evidence if the penetration also requires smoke control.