Duct Vibration Isolator 1-Inch Deflection 300 lb Spring
- Higher load capacity suits heavier equipment-bearing duct sections.
- The resilient element complements the steel spring in the support path.
Carry a heavier suspended assembly while allowing controlled movement
The 300 lb nominal spring hanger is a candidate for heavier duct or silencer support points requiring approximately 1 inch of working deflection. The steel spring provides vertical compliance; the housing transfers the load to the upper attachment and the specified resilient seating prevents a direct metal path at the seat. Selection must cover the entire suspension, including the rods, connections and building anchors.
Capacity and deflection are separate checks
A 300 lb designation does not establish the allowable load of the surrounding structure or permit an unspecified overload. Obtain the actual spring working range, rate, loaded dimensions and remaining travel. Too much compression can exhaust travel; too little compression on an unnecessarily stiff spring can reduce vibration isolation. The desired result depends on the relationship between the suspended system's natural frequency and the machine's operating frequencies, not simply on choosing the strongest hanger.
| Nominal reference | Project requirement |
|---|---|
| 300 lb support class | Calculated reaction at each location, including insulation, doors, accessories and other supported weight. |
| 1 inch / 25.4 mm deflection | Deflection at the specified operating load, with sufficient working travel. |
| Open housing, coated spring and neoprene seating | Assembly drawing, rod and washer interfaces, clearances and environmental suitability. |
Plan safe installation and future access
Use a coordinated temporary-support and load-transfer procedure for a heavy assembly. Adjustment or replacement must not leave the duct supported by an unverified remaining hanger. Locate adjustment points where technicians can observe the spring and reach the hardware without bearing their weight on the duct.
Keep rods and washers clear of the casing throughout the permitted movement. Any 30-degree allowance must be established for the selected assembly; it does not turn the hanger into a lateral brace. If seismic or other restraints are required, design them to accommodate normal isolated movement while performing their restraint function.
At handover and after equipment alterations, check spring seating, loaded height, clearance and signs of corrosion or resilient-element damage. A flexible duct connector cannot correct an unsuitable support arrangement or carry this suspended load.
Define a reviewable supply package
Send the weight schedule, centre of gravity, support plan, vibration source speeds and required static deflection. The quotation should distinguish hangers, rod hardware, resilient options, restraints and structural attachments. Require documented spring selection and installed-condition records; numerical isolation efficiency and seismic capacity need separate evidence.
Planning your Duct Vibration Isolator 1-Inch Deflection 300 lb Spring specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.