Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Duct Airflow Measuring Station 600 x 600 mm Differential-Pressure
zhengfeng-DUCT-AIRFLOW-MEASURING-STATION-600X600

Duct Airflow Measuring Station 600 x 600 mm Differential-Pressure

A multi-point pressure array feeds a separate airflow calculation and control loop, with transmitter range and fault response matched to operating duty.
  • Broader sampling coverage suits medium duct sections.
  • Remote control integration supports fan-speed supervision.
Request a Quote Browse Products

Airflow feedback for a controlled fan system

This 600 mm square station uses a multi-point total/static pressure array in a nominal 0.360 m² airway. It provides a pressure input from which a controller can calculate volume flow and supervise a fan or ventilation branch. The station is a sensing assembly: a drive, controller and suitable control sequence are separate parts of a functioning airflow loop.

Match the calculation to the signal

The listed 0–10 VDC signal represents differential pressure, not a linear percentage of airflow. Configure its pressure span and the station's calibrated pressure-to-flow relationship before setting a flow target. Density and units must match the calibration basis. Where a replacement transmitter has internal square-root processing, the controller must not repeat the same conversion.

Listed itemDesign consequence
Opening600 x 600 mm nominal; coordinate internal airway and outside sleeve dimensions separately.
Nominal section0.360 m²; use the calibration's specified area rather than an assumed net opening.
MeasurementMulti-point pressure averaging with total-to-static differential.
Analog range0–10 VDC proportional to pressure; confirm power supply and compatible controller input.
IntegrationFlow calculation, alarms and VFD control provided by the selected controls arrangement.

Stable measurement and stable control are different checks

Pressure fluctuations near a fan or throttled damper can produce a changing input. Appropriate siting, sampling and signal filtering help, but excessive smoothing can hide a rapid ventilation loss. Agree the control response, alarm delay and behaviour on a missing or implausible signal. A fan should not be driven to an unsafe limit merely because a disconnected tube appears as low airflow.

The minimum operating flow deserves its own range check: differential pressure becomes small as velocity falls. A sensor that reads design flow adequately may not resolve a low setback target. Review whether the selected pressure technology and transducer can serve the entire operating range before specifying one universal setting.

Installation and maintenance access

Coordinate the station with elbows, transitions and dampers using the manufacturer's siting requirements. Keep the sampling frame aligned and supported without twisting its ports. Route the two pressure lines together where practical, identify high and low connections and protect them from damage and condensate. Access must allow tube inspection, port cleaning and transmitter calibration without dismantling a main branch.

During service, distinguish changing filter resistance from a sensing fault by comparing fan state, independent pressure or flow readings and tubing condition. Do not compensate for a blocked pickup by increasing a software coefficient.

Order and commission the complete loop

Provide the flow setpoints, operating range, duct arrangement, electrical input and required alarms. Itemize the sensing assembly, transducer, controller work, drive interface and commissioning in the quote. Acceptance should check scaling, station conversion, independent airflow comparison and control response at minimum, normal and maximum duty. Prove the agreed fault response and retain settings. The station does not itself certify room pressure or cleanroom classification.

Planning your Duct Airflow Measuring Station 600 x 600 mm Differential-Pressure specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us