Home / Products / Air Ducts & Air Distribution / Duct Airflow Measuring Station 300 x 300 mm Differential-Pressure
zhengfeng-DUCT-AIRFLOW-MEASURING-STATION-300X300

Duct Airflow Measuring Station 300 x 300 mm Differential-Pressure

A compact total/static pressure array supplies a pressure-proportional signal for branch airflow calculation using the selected station relationship.
  • Multiple pick-ups sample across the small duct section.
  • Analog output interfaces with a separate monitoring controller.
Request a Quote Browse Products

Measure a small branch without treating voltage as airflow

The 300 x 300 mm station places an averaging pressure array across a nominal 0.090 m² duct section. Total and static pressure connections feed a matched differential-pressure transducer, allowing a controller to calculate branch volume. This helps distinguish an actual ventilation change from a damper command or fan-running indication, neither of which measures the air delivered.

The listed 0–10 VDC output is proportional to pressure. It must first be scaled to the transducer's pressure range and then converted using the supplied station relationship. For an ideal velocity-pressure measurement at fixed air density, velocity varies with the square root of differential pressure; a calibrated array may use its own coefficient or exponent. Applying a simple linear voltage-to-flow conversion, or applying square-root extraction twice, gives the wrong result.

Small-branch selection points

ItemReference and implication
Nominal duct300 x 300 mm; confirm actual internal dimensions and the area used by the calibration.
Geometric area0.090 m² before deductions; not a certified effective area.
Pressure samplingAveraging total/static array; orientation and connected ports must match the flow direction.
Output0–10 VDC pressure signal; supply voltage, load, common and pressure span require the electrical schedule.
Flow processingStation-specific relationship in the controller; agree density basis and output units.

At low branch flow the available differential pressure falls rapidly. Select the transducer for both minimum and maximum duty, with zero stability and resolution appropriate to the low end. An oversized pressure span may make the low-flow trend unhelpful even though the station fits the duct. No measurement accuracy or minimum detectable flow is established by the 300 mm size.

Locate and connect the measuring section

Give the supplier the positions of elbows, transitions, dampers and fans. An array combines samples but cannot automatically correct a badly distorted or reversing profile. Use the selected station's installation distances or a specified flow conditioner. Keep pressure tubes identified, airtight and free of kinks, water traps and construction dust; provide access for inspection and zero checks.

Service and acceptance

Unexpectedly low readings can arise from real low flow, reversed pressure tubes, a leaking line or blocked ports. Diagnose those causes before changing a calibration coefficient to force the display to match a target. Follow the sensor's cleaning instructions and avoid pushing contamination into the transducer.

For quotation, specify branch flow range, duct geometry, nearby fittings, air condition and BMS input. Separate the array, transducer, power supply, controller calculation, wiring, installation and balancing. Commission by checking zero and signal scaling, then comparing calculated flow with an agreed independent method at several operating points. Record the coefficient, units and alarm threshold. This station supplies measurement; it does not regulate the branch by itself.

Planning your Duct Airflow Measuring Station 300 x 300 mm Differential-Pressure specification?