Die-Cast Aluminum Raised Access Floor 53% Open-Area
- Free area verified on the selected panel drawing
- 62 mm die-cast panel body
- High-volume recirculation geometry
A deep open-grid module for recirculation paths
This configuration uses a nominal 62 mm die-cast aluminum body on a 600 × 600 mm grid. The 53% designation identifies a high-open-area selection; where more than 53% free cross-section is required, the supplied panel drawing must establish the value and how it is calculated. The deep ribs support the open face and create a different structural arrangement from a solid panel with added holes.
Large free area is only part of the airflow calculation
The available flow depends on pressure difference, opening geometry, underside ribs and the clear path into the plenum. Select the panel with pressure-loss data at the required airflow. A large geometric percentage cannot guarantee a room air-change rate or particle classification.
Keep service trays and equipment bases from blocking designated return locations. The panel is an airflow path, not a filter. If contamination can enter the service void, the room design must provide the appropriate cleaning and contamination-control arrangements.
Support the open face for actual traffic
Small wheels, equipment feet and lifting accessories need sufficient contact area on the remaining webs. Check wheel passage, concentrated load and deflection against the exact panel and supports. A high free area does not imply the same capacity as an adjacent solid module. Dedicated equipment support may be required beside or above the grating.
Coordinate the 62 mm depth with adjoining panels and the finished floor level. Pedestal height and bracing are project-dependent; the slab and anchors must carry the completed floor and equipment. Avoid site modification of cast ribs. Any planned aperture needs a separately reviewed detail.
Access, finish and acceptance
Select a coating or other finish that preserves opening geometry and suits cleaning and electrical requirements. Remove debris from the grate and seating surfaces, inspect coating wear and restore specified electrical connections after lifting. Record module positions because replacing one with a solid panel changes room airflow.
The quotation should cover the exact grate drawing, finish, understructure, transitions, dedicated supports and commissioning. Obtain assembly mass for slab calculations instead of assuming a generic system weight. Acceptance should combine fit and load documentation with the specified free-area verification and measured airflow at the installed operating condition.
Planning your Die-Cast Aluminum Raised Access Floor 53% Open-Area specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.