Constant Air Volume Terminal Box DN600 High-Capacity
- Large inlet accommodates main-branch distribution.
- Body length coordinated with inlet and service clearances
Active control of a large distribution branch
The DN600 CAV terminal provides an actively regulated large airway for a principal supply branch. Its pressure-averaging probe and electric control loop reposition a double-skin damper to maintain the selected volume within the available flow and pressure range. A large inlet alone does not establish a capacity rating or adequate control at every operating point.
Resolve connection size before fabrication
The reference layout uses a 600 mm inlet and 585 mm body length. The associated 24 in size class must not be treated as an exact dimensional conversion: 24 in equals 609.6 mm. Use the actual supplied spigot diameter, flange or coupling detail and tolerances when ordering the connecting duct.
A short regulating body does not mean a short complete installation. The airflow probe needs its specified inlet approach, and the actuator, controller and broad blade need clearance for service. Provide supports that preserve casing alignment rather than using the terminal to pull misaligned duct sections together.
Coordinate the branch with the central system
| Condition | Design implication |
|---|---|
| Normal setpoint | Select a reliable sensor signal and sufficient pressure for the downstream network. |
| Reduced-duty setpoint | Verify that the large inlet can measure and control the lower flow. |
| Downstream changes | Rebalance individual outlets; constant total volume does not preserve each branch quantity. |
| Control or power failure | Specify damper behavior, alarm and coordination with extract systems. |
The reference construction includes 22-gauge galvanized steel, a rubber-sealed double-skin blade, aluminum probe and brass bearings. Specify materials and structural suitability for the actual pressure and exposure. A stainless option must identify all affected components, and neither material choice proves a shut-off leakage class.
Commission the network, not only the controller display
Verify flow independently, check controller scaling and document the operating range and setpoints. Confirm that the central fan and terminal controls remain stable as other branches change. Room-pressure performance and emergency operating sequences require separate system checks.
The quotation should include complete dimensions, supports, control enclosure, electrical interfaces, sound requirements and commissioning. Keep access for probe cleaning, tube inspection and actuator replacement. A disturbed or blocked sensing path can cause incorrect regulation even when the damper still moves.
Planning your Constant Air Volume Terminal Box DN600 High-Capacity specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.