Constant Air Volume Controller DN100 Self-Powered
- No external energy is needed for basic constant-flow operation.
- The small-bore format suits localized supply or extract branches.
Keep a small branch near its selected airflow
The DN100 controller uses airflow forces acting on a blade against a spring mechanism to adjust resistance as duct pressure changes. A damping element limits oscillation, while an external scale selects the flow setting. Basic regulation needs no electrical supply. It can simplify a fixed-duty branch where a manual balancing damper would allow flow to drift when other branches change.
Small diameter does not establish a usable flow range
Select the operating flow from the supplied controller's tested range. A small bore can produce high velocity and regenerated noise at a substantial volume, while a very low setting may fall outside stable mechanical regulation. The usable range and accuracy depend on the selected mechanism and test conditions. Request the actual flow-pressure curves and the conditions under which tolerance is stated.
| Reference feature | Selection task |
|---|---|
| DN100 circular galvanized casing | Coordinate actual spigot dimensions, joint type and pressure duty. |
| Blade, spring and damping mechanism | Identify the operating pressure interval at the chosen setpoint and the air quality permitted through the mechanism. |
| External mechanical scale | Provide access for setting, locking and recording the commissioned value. |
The controller cannot create pressure or increase a starved branch beyond the available fan duty. At the other extreme, dissipating excessive pressure across the blade can create noise. Include downstream filters and terminals in the pressure calculation, including their loaded condition. A fixed supply volume alone does not regulate room pressure or prove adequate capture at a laboratory opening.
Install for repeatable mechanical response
Follow the selected unit's airflow direction, mounting and inlet requirements; do not copy another manufacturer's straight-length allowance. Keep fasteners and sealant clear of the moving parts. Insulation must not bury the setting mechanism, and casing treatment should be distinguished from a silencer that addresses sound carried along the duct.
Protect the unit from construction debris. If flow later changes, inspect for obstruction, damaged damping parts, air leakage or insufficient duct pressure before altering the setpoint. Do not bend the spring or lubricate components with unspecified materials.
Quote and verify the intended duty
Provide the required flow, minimum and maximum available pressure, upstream layout and air conditions. Identify end seals, acoustic treatment and stainless construction separately. Acceptance should compare independent airflow measurements with the agreed tolerance at representative system pressures and record the final setting; no universal precision or laboratory containment performance is implied.
Planning your Constant Air Volume Controller DN100 Self-Powered specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.