Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Cleanroom Doors, Windows & Interlocks / Compact HPL Cleanroom Door Paper-Honeycomb Core
zhengfeng-COMPACT-HPL-CLEANROOM-DOOR-PAPER-HONEYCOMB

Compact HPL Cleanroom Door Paper-Honeycomb Core

A laminate-faced personnel leaf combines paper-honeycomb infill, aluminum edges, a scheduled observation unit and an automatic bottom gasket.
  • The defined window format simplifies coordination of sightlines.
  • Aluminum edging protects the perimeter of the laminate faces.
  • A drop seal supports a clear floor passage during opening.
Request a Quote Browse Products

Laminate-faced access with a scheduled vision light

This single hinged door combines compact HPL faces, enclosed paper-honeycomb infill and aluminum edging. Its 400 x 600 mm double-glazed light provides a defined observation area within the nominal 900 x 2100 mm door format. Window size alone does not define a useful sightline: the mounting height, glass edge treatment and approach from either side must be shown on the elevation.

Compact HPL is the facing material in this sandwich construction, not a description of a solid laminate leaf throughout. The faces and bonded core work together, while the perimeter and designated reinforcement provide support for the hinges and lock. An aluminum edge protects the laminate perimeter but does not make all joints watertight.

Reference build and selection decisions

ItemListed configuration
Nominal size900 x 2100 mm; clear passage and frame opening shown separately.
Face/coreCompact HPL with paper honeycomb; select laminate grade, thickness and cleaning compatibility.
Frame50 mm aluminum alloy reference profile; wall fit and hardware support detailed on the section.
Vision400 x 600 mm rectangular double glazing; distinguish unit size from visible glass size.
Hardware304 stainless lever, automatic drop seal, handed hinges and optional hydraulic closer.

The listed flame-retardant paper treatment needs its own material evidence if required; it cannot establish a rated door. HPL chemical resistance also varies with the selected surface and the concentration, temperature and contact time of the cleaner. Include the edge seals and adhesives when reviewing a cleaning procedure.

Installation, sealing and maintenance

Protect the core from water entry at glazing joints, damaged edging and hardware penetrations. Avoid field cuts that leave the paper interior exposed. Fit the frame without twisting it and check the floor under the drop seal. The gasket should contact the intended landing surface when closed and retract without dragging when open; excessive travel does not compensate for a badly uneven floor.

Inspect laminate chips, lifting edges, window seals and lower-corner damage. Replace worn seal profiles with matching parts and investigate recurring water marks before cosmetic repairs. A decorative HPL finish should not be mistaken for a maintenance-free disinfectant barrier.

Quotation and acceptance

Schedule the laminate finish, complete dimensions, vision elevation, hardware, seals, wall work and installation as priced scope. Acceptance should compare the approved sample and drawing with the delivered door, measure clear passage, demonstrate the observation view and check full opening, latching and bottom-seal action under operating room pressure. Any specified leakage or fire performance requires evidence for that complete doorset.

Planning your Compact HPL Cleanroom Door Paper-Honeycomb Core specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us