Combination Fire and Smoke Damper 914 x 914 mm Class I
- A single-section square opening suits substantial duct branches.
- The expanded blade bank distributes closure across the full height.
A broad blade bank for a main duct penetration
The 914 x 914 mm combination assembly uses linked 3V steel blades in a galvanized frame, driven externally. It is intended for a main supply or return location requiring both fire protection and smoke-leakage control. The blade bank closes multiple passages together rather than deploying a stored curtain.
The Class I designation is a procurement requirement that needs model-specific smoke-leakage evidence. The size, actuator, pressure and temperature conditions must fall within the approved construction. A rating for a smaller damper or a similar blade profile cannot be assumed to cover this opening.
Frame geometry is part of reliable closure
| Item | Catalog arrangement |
|---|---|
| Nominal opening | 914 x 914 mm. |
| Frame | Galvanized steel. |
| Blades | Formed 3V linked bank with blade-edge and perimeter sealing. |
| Drive | External linked actuation. |
| Options | Position switches, selected electric or pneumatic drive and connecting sleeve, subject to assembly approval. |
A large frame can rack if the surrounding duct is misaligned or used to support it incorrectly. Even slight misalignment can affect several blade ends. Check the frame diagonals, blade clearances and sleeve position before energizing the actuator. Retaining components and thermal expansion space must follow the exact installation detail.
Actuation and main-system operation
The linked drive must move the complete bank under its required dynamic pressure. Actuator number, mounting and linkage are part of the qualified assembly, not field choices based solely on a torque estimate. Define the alarm signal, thermal override, fail position and fan/smoke-control sequence for this main branch.
A main return closure can affect several rooms. Commission the damper with the intended ventilation controls so the response is documented. Position switches indicate travel; visual checks establish that all blades move, while the specified leakage class comes from the appropriate qualification.
Access and acceptance
Provide access to the external drive and the full bank for inspection, cleaning and approved component replacement. Paint and cleaning residues must not bind the seals or pivots. The service plan must preserve the certified actuator/control combination.
Purchase the identified assembly with its sleeve, retaining components, controls, feedback and supporting documents. Acceptance should establish the approved single-section or assembled arrangement for 914 mm size, barrier compatibility, functional closure and system response. Fire duration, smoke-leakage class and elevated-temperature operation are distinct ratings and should be documented separately.