Combination Fire and Smoke Damper 305 x 305 mm Class I
- A single assembly addresses both smoke leakage control and thermal closure.
- External actuation keeps the drive accessible outside the air passage.
Linked blades with thermal and smoke-control functions
The nominal 305 x 305 mm assembly uses linked formed-steel blades and an external drive. Blade-edge and perimeter seals limit leakage when the bank closes. The combination designation addresses both fire closure and smoke control, which need separate applicable evidence for the supplied assembly.
Class I in the product designation identifies the requested smoke-leakage selection. It is not a zero-leakage claim or proof of certification. Acceptance requires the relevant rating, pressure and temperature conditions for the actual model and actuator.
Compact body, accessible drive
| Item | Reference configuration |
|---|---|
| Opening | 305 x 305 mm nominal. |
| Frame | Galvanized steel. |
| Blades | Linked formed 3V steel profile. |
| Drive | External actuation, with selected supply and controls. |
| Options | Position indication and sleeve length within the approved construction. |
| Required evidence | Fire rating, smoke-leakage class, dynamic airflow/pressure and elevated-temperature duty for the assembly. |
The actuator may project beyond a small duct footprint. Position it toward a permanent access opening that allows inspection and replacement; an external actuator can still become inaccessible behind a finished wall. Sleeve length and actuator position must remain within the permitted installation.
Specify the control sequence as a complete system
A smoke command may need closure before the thermal release operates. The alarm interface, thermal override, power-loss action and any permitted reopening sequence must follow the approved controls and building design. A generic actuator selected only by torque or voltage is not automatically an acceptable substitute.
Position contacts should be checked against actual blade travel. A closed signal does not demonstrate the smoke-leakage class. A functional control test and a leakage qualification answer different questions.
Installation, service and procurement
Follow the exact sleeve, retaining, expansion-clearance and duct-connection instructions for the approved barrier. Avoid coating seals or adding sealant that obstructs movement. Inspect the linkage, blades and thermal device through the planned access; replacements must preserve the approved assembly.
The quotation should identify actuator and supply, interface contacts, thermal controls, sleeve and retaining parts, access and documentation. Acceptance should verify traceable fire and smoke qualifications, correct installation and the specified alarm/power-loss sequence with visual blade confirmation. Neither a 3V profile nor Class I wording establishes a rating by itself.
Planning your Combination Fire and Smoke Damper 305 x 305 mm Class I specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.