zhengfeng-CLEANROOM-RETURN-AIR-GRILLE-800X350

Cleanroom Return Air Grille 800 x 350 mm

An elongated room-side grille and recessed box accommodate one broad panel filter, with full-width removal clearance and a supported sealing seat.
  • The long face suits spacious wall bays beside production equipment.
  • A single matching filter reduces the number of separate filter frames to manage.
Request a Quote Browse Products

A broad filtered opening along the room perimeter

The 800 x 350 mm return assembly accommodates a long 782 x 332 x 18 mm reference panel filter. It consolidates a return location within one broad wall face, which can simplify the arrangement beside production equipment. The single wide element also creates a larger removal and handling envelope than a compact filter.

One long grille is not automatically equivalent to several distributed returns. The duct connection and internal box determine how air reaches the branch, while room obstructions determine where the air comes from. For a long room or divided work area, compare the collection pattern with several return locations before consolidating them.

Dimensions for coordination

ComponentCatalog reference
Face800 x 350 mm.
Body260 mm depth.
Panel filter782 x 332 x 18 mm; verify exact frame tolerances, seating and retention.
Metal choiceAluminum or stainless steel.
PositionLow wall with flush room-side front.

Show framing around the long opening and keep the filter seat straight. Duct or partition loads must not bow the housing. Leave room below and in front for the access face to open or be removed and for the full filter to be withdrawn without bending it around equipment.

Filter grade and operating resistance

F5/F8 in the original listing describes legacy filter choices, not a verified ISO 16890 or HEPA classification for this product. Specify the actual element's standard, reported class and resistance at the intended flow. There is no direct class conversion between EN 779 and ISO 16890; a matching face dimension alone is not sufficient replacement evidence.

A wider filter can offer more area at a fixed return quantity, but it must still be supplied with its own pressure data. As the element loads, the system may lose return flow or alter room pressure unless the controls compensate. Evaluate replacement limits against the ventilation design and process conditions.

Keep the long seal path intact

During replacement, support the element by its frame and inspect all edges for bypass gaps or distortion. Clean deposits from the housing without sending them into the duct or wetting replacement media. A washable grille does not imply washable filter media. Select the exposed metal and finish for the actual cleaning agents.

Request pricing for the complete grille and box, filter and spares, connection orientation, wall trim and monitoring points. Acceptance should cover frame straightness, service clearance, filter seating and measured return flow, plus room airflow or pressure checks required by the project. A low-level filtered return does not establish hazardous-material containment or a cleanroom classification on its own.

Planning your Cleanroom Return Air Grille 800 x 350 mm specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.