Home / Products / Air Ducts & Air Distribution / Cleanroom Pressure Relief Damper 15 Pa
zhengfeng-CLEANROOM-PRESSURE-RELIEF-DAMPER-15PA

Cleanroom Pressure Relief Damper 15 Pa

A balanced mechanical blade provides a passive relief path around a nominal 15 Pa target when the ventilation balance supplies the required pressure.
  • Self-Powered Blade with Mechanical Balance
  • A wall or duct connection gives flexibility in the transfer-air route.
Request a Quote Browse Products

A passive transfer path around a 15 Pa target

This relief damper uses a balanced airfoil blade to respond directly to pressure across a wall or duct. The 15 Pa designation identifies the intended low differential-pressure setting. A mechanical weight moment opposes opening; increasing pressure moves the blade and allows more transfer air through the selected path.

The device does not create room pressure. Supply and extract imbalance, room leakage and the downstream pressure establish the air available for relief. If that balance disappears, a passive blade cannot maintain 15 Pa by itself.

Low differential means installation details matter

ItemCatalog selection
Target setting15 Pa, to be established in the installed operating condition.
MechanismSelf-powered balanced airfoil blade with adjustable weights.
MaterialsExtruded aluminum, stainless pivots and nylon bearings.
MountingWall or duct arrangement with the specified pivot orientation.
OptionsProtective grille/louver, mill finish or powder coating.
Control accuracyRequire the supplied assembly's pressure/flow curve and demonstrated regulation band.

At a low setting, bearing friction, a tilted frame or dirt on a pivot can be significant relative to the opening force. Install the unit in its intended orientation with free blade travel. A grille or connecting duct adds resistance, so room-to-room differential is not necessarily the same as pressure directly across the blade.

Select the relief quantity as well as the pressure

The needed opening area follows the surplus air that must leave the room over the operating range. A small unit may reach its open limit before relieving the required quantity. Conversely, a large blade may operate near its most sensitive range at low flow. Use the actual pressure/flow relationship with the complete transfer route.

A doorway opening can bypass the intended relief path and collapse the differential. The relief damper is not a substitute for room-pressure monitoring or a transfer strategy appropriate to contamination control. An unfiltered connection must be evaluated for the intended direction and process.

Commissioning and maintenance

Keep pivots and stops clean without adding unapproved lubricant or altering weights casually. Record the final weight arrangement. Quote the clear opening, frame, protective face, setting and pressure/flow test scope. Commission at minimum and maximum normal ventilation conditions with relevant doors closed, using defined pressure reference points. Record setting, flow and pressure stability; a ±3 Pa promise cannot be inferred from the nominal 15 Pa name.

Planning your Cleanroom Pressure Relief Damper 15 Pa specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team