Cleanroom HEPA Terminal Housing 305 x 305 mm
- Compact frame suits individual ceiling filtration points.
- Retainers support the element during room-side replacement.
A small terminal point with a separately selected filter
This welded ceiling housing holds a replaceable 305 x 305 mm filter at the final supply point. It suits a small individual terminal where the ceiling layout cannot accommodate a larger module. The housing positions the filter and closes the path around its frame; particle removal comes from the selected element. A compact case alone does not establish airflow capacity, HEPA efficiency or a room cleanliness class.
Fit the seal and filter depth before the ceiling opening
| Catalog item | Selection meaning |
|---|---|
| Filter face | 305 x 305 mm; filter depth and frame profile must also match. |
| External frame | 392 x 392 mm reference size; this is not a ceiling cut-out dimension. |
| Housing | Welded construction, with room-side element replacement. |
| Seal choices | Flat/DIN-type, PU gasket or gel interface, as specified for the chosen filter and casing. |
| Retention | Tool-free clamping and pre-positioning supports in the listed arrangement. |
| Air entry and face | Top or side entry; optional perforated diffuser. |
The seal choices require different mating details. A compressible gasket seats against a suitable contact surface; a gel-seal element needs the corresponding sealing blade and engagement geometry. The word DIN is not a complete seal specification. Select the exact profile, element depth and clamping travel together rather than assuming all 305 mm filters interchange.
Airflow and ceiling coordination
At a given volume flow, a smaller filter face carries more air per unit face area than a larger one. Select from the actual filter pressure-drop curve and terminal acoustic data, allowing for the system's available pressure as the filter loads. Excessive throttling at a small inlet can add noise; a larger terminal or revised branch may be preferable when the duty exceeds the selected assembly's data.
Show the neck dimensions, inlet orientation, casing depth, suspension points and access zone on the installation drawing. False-ceiling, suspended and T-grid installations require the corresponding mounting detail. Duct weight must not distort the sealing seat. Below-ceiling access must allow the face to open and the filter to pass out without contacting nearby equipment.
Service, quotation and acceptance
Keep the sealing seat clean, handle a replacement element by its frame and check the retainers before releasing its weight. The supports aid positioning; they do not justify an unspecified one-person lifting procedure. Filter replacement is based on condition and the facility's maintenance limits, while housing replacement is normally driven by damage or an interface change.
Specify whether the quote includes the element, diffuser, inlet damper, suspension hardware, pressure taps and aerosol test access. Acceptance should cover dimensions, secure retention, measured airflow and the agreed installed-filter leakage test. Pressure-drop readings are useful for monitoring but do not establish that the seal is intact. Record the filter identification and initial pressure reading for later service comparisons.
Planning your Cleanroom HEPA Terminal Housing 305 x 305 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.