Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Cleanroom Flexible Air Duct DN200 R-8 Insulated
zhengfeng-CLEANROOM-FLEXIBLE-AIR-DUCT-DN200-R8

Cleanroom Flexible Air Duct DN200 R-8 Insulated

A medium flexible inlet needs suitable approach geometry and clearance around its insulation.
  • Broader lined bore serves medium terminal connections.
  • Reinforced jacket protects the insulation during handling.
Request a Quote Browse Products

A flexible inlet connection needs room to develop flow

The DN200 insulated flexible duct connects a medium air terminal or distribution branch where limited alignment adjustment is useful. A wire-supported woven liner forms the air passage, an insulation blanket limits heat transfer, and a reinforced metallized jacket protects the insulation enclosure. The assembly should be selected as a short connecting run with a defined pressure loss.

The bore reference is 8 inches, approximately 203 mm. Check the actual spigot dimensions before choosing clamps or collars. A bend immediately against a flow pickup, control box inlet or fan connection can produce an uneven velocity pattern. Follow the connected equipment requirements for inlet geometry; a conveniently shaped hose does not remove its need for a suitable measurement or entry section.

Thermal selection and operating limits

SelectionWhat it establishes
R-8 designationThe required insulation variant, subject to the delivered product label and stated thermal test method.
7.62 m reference coilA supply format, separate from the designed installed length.
Positive and negative pressureSeparate service limits for the actual liner, helix and connection construction.
Outer jacketAn enclosure needing continuous end seals and compatible protection from its environment.

An insulation value does not prove a pressure, temperature or fire rating. Use documented values applying to the same supplied variant and size. Allow the full insulated outside diameter through the ceiling cavity; squeezing the blanket to clear another service reduces its useful thickness and can create a condensation-prone location.

Install and diagnose the complete connection

Extend the liner, remove unnecessary surplus and arrange broad supports without flattening the airway. Seal the inner air connection independently of the outer jacket closure. Support the terminal separately so its weight is not carried by the flexible run.

If the terminal falls short of airflow, inspect sag, compression, collars and inlet geometry before changing the controller calibration. Maintain access to joints and follow a liner-compatible cleaning method. Where cleanroom service requires particular shedding, chemical or hygiene evidence, assess the actual liner and its location in the filtration system.

Quotation and handover

Provide the terminal model, route sketch, airflow, pressure conditions, insulation requirement and collar dimensions. Identify duct, connection accessories and supports in the price scope. Handover evidence should include the supplied variant data, installation inspection and terminal airflow verification under the intended system conditions.

Planning your Cleanroom Flexible Air Duct DN200 R-8 Insulated specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us