Cleanroom Door Status Indicator LED with Request Button
- One station groups the request and its visible feedback.
- Momentary action suits a controller request input.
- No sounder is included in this configuration.
A local request and its indication in one place
The combined station places a momentary button beside red-green status LEDs. It gives users a clear action point at a controlled entrance while reducing the wall space needed for separate accessories. The selected configuration has no sounder, making it suitable where visual guidance is preferred.
The button and the LEDs have different roles. Pressing generates a request to the external controller; the lights display the state returned by that system. A pressed button should not automatically be treated as permission to enter an airlock whose other door or process conditions prevent release.
Make the response understandable
Define what users see before pressing, while the request is pending and after permission is granted. If only two colours are available, keep the meanings simple and consistent with nearby stations. An indicator driven directly by the button may acknowledge a press without representing the actual door state.
Decide how the controller handles a held button and repeated presses. A momentary contact does not establish queuing, priority, automatic retry or emergency override. Those behaviours belong to the controller sequence and should be tested rather than inferred from the station hardware.
Two circuits to coordinate
| Connection or feature | Required definition |
|---|---|
| Button contact | Resting state, contact form and rating for the request input |
| LED control | Red and green meanings with the appropriate common or return |
| DC reference | 10–24 VDC configuration, checked for the supplied station |
| AC option | Separately verified AC limits, without assuming the same upper limit as DC |
| Housing | Combined curved indicator and physical button, without buzzer |
| Mounting | Reachable location with matching preparation or backbox |
The indicator supply does not establish the electrical rating of the button contacts. Likewise, a controller input should not receive the lamp supply merely because both functions share a housing. Use the exact terminal diagram and keep any required circuit isolation intact.
Place, clean and test as a user station
Position the button where users can operate it before reaching the door movement area. Check visibility from the approach and usability with the gloves normally worn. The button remains a shared touch surface, so include it and the housing joint in the cleaning procedure.
Acceptance should include an ordinary request, denial while another door is open, a held button, repeated presses and power restoration. Verify that the button releases freely and that the LEDs show the agreed controller state. Record the state sequence and connections for maintenance. Where touchless activation is required, retain a separate suitable sensor rather than treating the integrated mechanical button as contact-free.