Cleanroom Ceiling Air Diffuser 1200 x 300 mm Rectangular Cone
- Long panel aligns with narrow rectangular ceiling grids.
- Localized cone retains a four-way supply pattern.
A long ceiling panel with a localized air outlet
The 1200 x 300 mm rectangular panel contains a 300 x 300 mm active square cone. Its blank extension fills a narrow ceiling bay, while supply air leaves at the cone location. This is useful in a corridor or long ceiling module where a separate small square fitting would require additional infill.
The long panel is not a continuous slot diffuser. Increasing the blank-panel length adds no active discharge area. Outlet spacing must follow the cone's tested distribution at the design airflow, rather than the overall 1200 mm panel dimension.
Geometry to show on the ceiling drawing
| Element | Catalog arrangement |
|---|---|
| Nominal panel | 1200 x 300 mm, lay-in construction. |
| Active face | 300 x 300 mm square cone, localized within the panel. |
| Panel finish | White-coated formed steel. |
| Discharge | Four-way horizontal at the cone. |
| Access | Removable square core. |
| Connection | Circular neck behind the active face. |
| Options | Alternative panel frame and compatible inlet damper. |
Dimension the cone centre, neck centre, panel edge and bearing detail. The neck is not necessarily at the centre of the full panel. Coordinate the blank area with lights, detectors and access panels without treating it as a field-cut service panel. A long narrow face also needs the support detail required to keep it flat and securely seated.
Does a four-way cone suit a corridor?
A narrow passage brings the side walls close to the outlet. Sideward jets can meet those walls before the desired longitudinal coverage develops. Compare the selected cone's throw with corridor width, ceiling height, door locations and terminal flow. Where distribution must follow the corridor length, evaluate a directional or linear outlet instead of assuming the rectangular panel creates a rectangular discharge pattern.
Select the neck from the active cone duty, including pressure and sound limits. Throttling a damper cannot change the blank extension into an outlet. Check minimum-flow operation as well as peak cooling duty, and coordinate return locations to avoid sending the supply directly into the extract path.
Access, pricing and acceptance
Keep the square core accessible below the ceiling and leave clearance above its neck for a supported duct connection. After cleaning, resecure the core and panel without bending the blank extension. Use cleaning materials compatible with the coating; inspect any insulation and vapour seal around cold-air connections if condensation is observed.
A useful quotation identifies panel and frame dimensions, cone position, neck diameter, damper, finish, support accessories and insulation. The acceptance record should include actual airflow, core retention, panel seating and room-distribution checks at the intended operating conditions. Neither the panel size nor the cleanroom application label establishes filtration or a room cleanliness class.
Planning your Cleanroom Ceiling Air Diffuser 1200 x 300 mm Rectangular Cone specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.