Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Cleanroom Air Transfer Grille 400 x 400 mm No-Sight
zhengfeng-CLEANROOM-AIR-TRANSFER-GRILLE-400X400

Cleanroom Air Transfer Grille 400 x 400 mm No-Sight

assess effective opening, air-path position, wall or door support and the limits of fixed visual screening.
  • Broad louver field suits larger transfer duties.
  • Fixed construction avoids adjustment hardware at the room face.
Request a Quote Browse Products

One broad opening for a planned transfer route

The 400 × 400 mm no-sight grille consolidates a room-to-room transfer path into a broad square opening. Fixed overlapping blades screen direct vision while pressure difference moves air through the core. This arrangement can simplify a wall elevation that would otherwise use several smaller openings, provided the selected duty and wall detail support it.

A broad opening changes more than face area

The nominal square area is 0.16 m², before allowing for the frame and louvers. Use the effective area and pressure-loss data of the complete fitting to select airflow and sound. A large core does not create the driving pressure and cannot guarantee the required transfer at every fan setting.

Concentrating transfer in one location changes the room flow route. An opening close to a supply outlet can short-circuit air before it reaches occupied or process areas. Furniture and equipment can obstruct the approach. Position the grille with the full supply, extract and room layout rather than choosing a convenient unused patch of wall.

Structural and dimensional coordination

ReferenceDetail to resolve
400 × 400 mm nominal coreDesign size, distinct from the final construction opening.
398 × 398 mm actual-core referenceVerify insertion clearance and frame engagement on the supplied drawing.
480 × 480 mm coverAllow sufficient border clearance from door rails and adjacent fittings.
Powder-coated aluminumSelect finish and cleaning compatibility for both exposed sides.

A wide cut-out can interrupt a door or panel support member. Specify reinforcement and perimeter closures where needed, without using the cover flange as an assumed structural repair. Any fire or smoke requirement applies to the complete modified assembly.

Keep the intended separation explicit

This passive opening can pass air in either direction. It is not a backdraft damper, a filter or an automatic pressure-control device. Visual screening also does not qualify acoustic or light isolation. Select a different documented transfer arrangement when the room boundary requires those functions.

Include airflow, pressure, sound, wall thickness, both-side frames, supports and access in the quote. Commission the transfer route in normal and reduced operating modes. During service, inspect for bent blades, blocked approaches and deposits inside the louvers, then restore the documented room balance after significant ventilation changes.

Planning your Cleanroom Air Transfer Grille 400 x 400 mm No-Sight specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us