Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Cleanroom Air Transfer Grille 200 x 200 mm No-Sight
zhengfeng-CLEANROOM-AIR-TRANSFER-GRILLE-200X200

Cleanroom Air Transfer Grille 200 x 200 mm No-Sight

specify pressure-driven airflow, door construction, visual screening and access to the louver passages.
  • Passive transfer path requires no motor.
  • Small square cover suits narrow door panels.
Request a Quote Browse Products

A small transfer opening that screens direct sight

The 200 × 200 mm no-sight grille provides a passive air path through a door or partition. Overlapping fixed blades interrupt the direct view through the opening while room pressure drives air through the passages. It is useful for a support room that needs transfer air without a plainly visible hole in its door.

Privacy does not establish isolation

The grille contains no fan or one-way control. Flow can reverse when the pressure relationship reverses, and very little pressure difference may produce inadequate transfer. Select the required airflow at the available room-to-room pressure, including the resistance of the complete grille arrangement.

No-sight describes visual screening. It does not establish light-tightness, acoustic privacy, particle filtration or smoke control. An opening between incompatible processes may defeat the intended separation even though the rooms cannot be seen through it. Where these functions are required, select a transfer assembly with the corresponding documented performance.

Fit the door as an assembly

Dimension or materialReference for coordination
Nominal core200 × 200 mm.
Reference actual core198 × 198 mm, subject to the supplied drawing.
Cover280 × 280 mm powder-coated aluminum face.
MountingDoor or partition with a thickness-matched fixing and rear finish.

The face overlap conceals the cut edge but does not reinforce the leaf or close an exposed hollow core. Coordinate the opening with rails, locks, seals and the door construction. A rated door or partition needs an assessed transfer detail; a generic grille must not be assumed to preserve its rating.

Keep the passage accessible

A low door location is vulnerable to impacts and cleaning debris. Provide access to both faces and the hidden blade passages, using a cleaning method compatible with the coating. Bent blades or accumulated material can affect both visual screening and airflow.

For quotation, state required transfer quantity, available pressure, door thickness, opening and cover dimensions, finish and any acoustic or compartmentation requirement. Include the complete front and rear fixing arrangement. Acceptance should check fit, secure edges, sight screening and measured transfer with doors in the specified operating position. Reassess the room balance when extraction or door-seal arrangements change.

Planning your Cleanroom Air Transfer Grille 200 x 200 mm No-Sight specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us