Bubble-Tight Isolation Damper 152 x 152 mm
- The compact passage suits localized isolation points.
- Replaceable perimeter sealing separates seal maintenance from the welded blade.
Compact isolation for a specified leakage duty
The nominal 152 x 152 mm damper uses a centre-pivoted double-skin blade inside a flanged steel body. A mechanically retained silicone perimeter seal closes against the frame, while the axle penetrations require their own seals. The compact square format suits a small process branch when an ordinary balancing damper cannot provide the specified shutoff.
Bubble-tight describes a leakage result under defined test conditions. It is not an unlimited zero-leakage promise. The supplied damper needs evidence at the specified pressure, flow direction and closing torque; naming AMCA 500-D identifies a test method, not a certification held by this product.
Construction and rating schedule
| Item | Catalog arrangement or required evidence |
|---|---|
| Opening | 152 x 152 mm nominal. |
| Blade/shaft | Centre-pivoted double-skin blade and full-length stainless steel axle. |
| Body options | Painted steel, 304L or 316L stainless steel. |
| Seal | Mechanically fastened silicone perimeter element; axle sealing included in the selected design. |
| Connection | Square flanges with selected drilling. |
| Operation | Manual or powered configuration. |
| Performance | Document permitted velocity, differential pressure, temperature and closed-leakage test for the supplied assembly. |
Small opening, complete actuator envelope
The flange and actuator can occupy considerably more room than the nominal passage. Leave external access for bearings, couplings and position switches and enough internal clearance for the blade to rotate. Support adjoining ducts so bolting does not pull the seat out of square.
Actuator selection requires breakaway and seating torque under the specified conditions, including seal friction and differential pressure. Select the required loss-of-power position and control signal explicitly. A closed-position switch reports travel; it does not prove leak-tight closure. Manual locking provisions and powered fail action serve different operating needs.
Seal compatibility, maintenance and acceptance
Silicone and the selected metal finish must suit the actual decontaminant, concentration, temperature and exposure duration. A broad temperature label does not establish chemical compatibility. Deposits on the seat, damaged silicone or a changed linkage stop can prevent sealing. Isolate the process before service and use the specified seal and adjustment procedure, followed by the agreed leakage recheck.
Price the body, actuator or hand mechanism, switches, mating gaskets, flange drilling and test documentation separately. Acceptance should distinguish blade/shaft leakage from leakage through the installed flange joints. Verify stroke, fail action where supplied, required closure torque and the test result at the purchase pressure. This process isolation damper is not a fire or smoke damper unless a separate approved construction is specified.
Planning your Bubble-Tight Isolation Damper 152 x 152 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.