Your One-Stop Supplier for Cleanroom Equipment and Aseptic Facility EssentialsInternational Project Support
Open mobile navigationClose mobile navigation
Home / Products / Air Ducts & Air Distribution / Backdraft Damper Vertical-Mount Discharge
zhengfeng-BACKDRAFT-DAMPER-VERTICAL-DISCHARGE

Backdraft Damper Vertical-Mount Discharge

An outlet-flanged gravity blade assembly responds to horizontal exhaust flow and returns toward its stops when forward pressure falls.
  • Outlet-side fixing supports sidewall discharge layouts.
  • Separate blades allow the opening to respond directly to exhaust flow.
Request a Quote Browse Products

Outlet-side mounting for a horizontal exhaust path

This backdraft damper mounts vertically with its flange on the discharge side. Forward exhaust pressure pushes the aluminum blades outward; their hanging arrangement brings them back toward the stops as airflow falls. The outlet-side flange suits access from the discharge face of a sidewall or duct connection.

The blades reduce reverse flow after closure, but do not establish a gas-tight boundary. The reverse leakage and pressure capability must be specified for the actual damper. Wind-driven pressure and repeated blade movement are relevant to a wall outlet even when the fan's steady-flow duty is modest.

Construction and selection schedule

ItemCatalog arrangement
Frame orientationVertical.
Forward flowHorizontal discharge.
Fixing flangeDischarge side.
MaterialsGalvanized steel frame, aluminum blades.
OperationAir-pressure opening and gravity closure.
Duty limitsEstablish opening pressure, forward loss, velocity and reverse-pressure rating from the supplied size's data.

Keep the outlet clear through its full stroke

A downstream hood, screen or wall trim can block blades even when the opening dimensions are correct. Show the complete moving envelope and maintenance access on the outlet detail. Keep the frame plumb and square, seal the flange joint and avoid fasteners projecting into the travel path.

The damper is not a rain louver. Weather protection, drainage and any guard must be selected as part of the outlet, with their added resistance included in fan selection. For a variable-speed exhaust fan, verify that the minimum duty opens the blades adequately. Start-open pressure refers only to initial movement; it does not describe pressure loss at the required flow.

Address chatter and deposits

Blade chatter may arise from gusting wind, low or uneven exhaust flow, nearby fan turbulence or sticking pivots. Inspect those conditions before changing the blade balance. Cleaning should remove deposits from the stops and bearings without adding arbitrary lubricants or extra weights. Recheck closure after service.

Specify opening size, outlet flange, wall depth, flow range, reverse pressure and access in the quotation. Include weather accessories and their pressure effects separately. Acceptance should demonstrate free travel, airflow at the intended fan settings, reliable return on shutdown and the agreed reverse leakage. Where a process needs positive commanded isolation or fire/smoke protection, choose a separately qualified device for that duty.

Planning your Backdraft Damper Vertical-Mount Discharge specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team
Inquiry Form

Home

Products

News

About Us

Contact Us