Antistatic HPL Raised Access Floor 40 mm Woodcore
- 600 x 600 x 40 mm panel
- Wood-based high-density core
- HPL face with sealed PVC perimeter
A dry-service panel with an HPL walking face
This reference 600 × 600 × 40 mm access panel combines a high-density chipboard core, antistatic HPL top, galvanized-steel underside and black PVC edge trim. The wood-based core forms the panel body while the facing, backing and perimeter protection complete the assembly. Approximate panel mass is 10 kg for handling planning; the supplied construction determines the final mass.
The panel suits dry control and technical rooms with frequently accessed cables. Edge protection reduces exposure during normal service, but does not make a woodcore panel suitable for washdown. Water entering a cut-out or damaged edge can cause swelling and loss of fit.
Support and loads belong to the whole floor
Select pedestal height, head details, stringers where required and anchoring from the equipment layout. Concentrated feet, rolling loads and uniformly distributed loads are different demands. A 40 mm thickness or panel weight does not establish a working-load class, and an ultimate failure load is not an allowable service load.
Plan equipment moves, perimeter panels and openings before installation. A cut panel may lose the load path of an intact module and require additional support. Floor height must leave room for services without obstructing pedestal stability or future access.
HPL and electrical interfaces
An antistatic HPL face does not establish a complete ESD floor. Define resistance and personnel-grounding requirements, then assess the facing, edge, panel contacts and understructure as the proposed assembly. Metal backing alone is not proof of a continuous ground path.
Line cable openings and protect exposed core edges. Keep the removable grid accessible; permanent furnishings should not prevent panels required for service from being lifted. Use a lifting tool compatible with the face and avoid storing removed panels on vulnerable corners.
Care, price and acceptance
Use controlled damp cleaning without flooding joints. Inspect damaged laminate, swollen edges and loose trim before refitting panels. Correct rocking by restoring the support arrangement rather than inserting improvised packing.
A quotation should identify panels, understructure, finished floor height, cut-outs, ramps, perimeter closures, grounding and tests. Acceptance should verify flatness, seating, removability, protected openings and load documentation for the complete selected system, plus electrical results where specified.
Planning your Antistatic HPL Raised Access Floor 40 mm Woodcore specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.