Antistatic HPL Raised Access Floor Encapsulated Calcium-Sulphate
- Six-face galvanized-steel enclosure
- Calcium-sulphate mineral core
- HPL finish on the enclosed panel
Six-face steel protection around a mineral panel
The encapsulated configuration encloses a calcium-sulphate core with galvanized steel before an HPL wearing face is applied. Its reference module is 600 × 600 mm with a nominal 28–30 mm thickness range. The metal continues around the core perimeter, providing a different handling edge from separately bonded PVC banding.
This construction is useful where repeated access exposes panels to handling wear. It does not make panels immune to dents, moisture ingress at joints or damage from incorrect lifting. The HPL and folded steel details still need protection when a module is removed or stored.
Encapsulation is not a load or water rating
Load capacity depends on the complete panel and its pedestal/stringer system. Specify concentrated feet, rolling loads, finished height and acceptable deflection, and obtain evidence for that assembly. A thinner encapsulated panel cannot be compared with a thicker banded panel from thickness alone.
The enclosure protects the core, but seams, penetrations and floor joints remain interfaces. Use this configuration in the specified dry technical setting; six covered faces do not constitute a waterproof room floor. Fire classification also needs the finished panel build, including HPL and adhesives.
Cut-outs interrupt the enclosure
A service opening cuts the steel shell and mineral core. Factory-planned apertures allow edge lining, burr removal and local supports to be coordinated. The unmodified panel rating should not be assumed to apply after cutting. Protect cables from sharp metal and prevent exposed core material shedding into the service void.
HPL described as antistatic still needs integration with the intended grounding design. Confirm how the walking surface connects through the panel and understructure, especially where insulating gaskets or coatings are present. Electrical continuity is a separate acceptance item from a visually complete steel enclosure.
Service access and quotation
Use the approved lifting tool, keep panel edges clear of debris and inspect folded seams for deformation before refitting. Correct rocking through the designed support system. Keep replacements with matching thickness and edge geometry.
The enquiry should state room grid, finished height, equipment loads, access frequency and apertures. Quote panels, HPL, understructure, cut-out reinforcement, perimeter closures and electrical tests separately. Handover should verify fit and removability, protected openings, system load documentation and the agreed grounding measurements.