Antistatic HPL Raised Access Floor Calcium-Sulphate Core
- High-density calcium-sulphate core
- Galvanized-steel underside
- Conductive PVC edge protection
Mineral core with separately protected edges
This 600 × 600 mm access-floor panel places an antistatic HPL face over a calcium-sulphate core, with galvanized-steel backing and conductive PVC edge banding. The perimeter is a separate trim rather than a six-face steel enclosure. It allows the edges to be inspected when a panel is lifted for service access.
The reference construction range is 30–40 mm panel thickness, approximately 1,650 kg/m³ core density and 0.3–0.5 mm steel backing. These describe possible builds, not interchangeable load classes. The order needs one defined core, thickness, backing and face combination supported by the required system evidence.
Why density and thickness are not enough
Panel behavior also depends on core formulation, backing bond, geometry and support. Specify concentrated equipment loads, rolling traffic, deflection criteria and the installed pedestal arrangement. Select fire and acoustic performance using reports for the complete construction; a mineral core alone does not qualify an HPL-faced floor assembly.
Plan cut-outs before manufacture. Removing part of the core and backing changes the load path, so opening size, position and additional support need review. Protect the exposed edge with a compatible liner or grommet. Do not use an intact-panel rating automatically for a modified module.
Access and electrostatic details
Conductive edge banding provides a component of the intended electrical arrangement, not proof of a grounded walking surface. Establish the required electrical path through finish, panel and understructure, with measurements for the finished installation where ESD control is specified.
Keep panels seated on the specified supports and maintain the planned grid around services. Damaged banding can expose a friable edge or disrupt the intended contact arrangement. Steel backing and edge trim do not make open joints suitable for repeated washdown.
Maintenance and procurement
Use controlled cleaning, protect corners during lifting and inspect edges before panels return to service. Replace damaged components with the specified build so height and fit remain consistent.
Separate panel construction, pedestals, stringers, bracing, openings, perimeter treatment and testing in the quotation. Provide finished height and service routes. Acceptance should check seating, level, access, protected cuts and the evidence for the exact load and electrical configuration.
Planning your Antistatic HPL Raised Access Floor Calcium-Sulphate Core specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.