zhengfeng-ANTISTATIC-EPOXY-FLOORING-NOVOLAC-08

Antistatic Epoxy Flooring Novolac Floor Coating

A shallow conductive novolac coating selected around the actual chemicals, electrical programme and floor connections.
  • Conductive novolac wearing formulation
  • Nominal 0.6–0.8 mm smooth layered build
  • Chemical resistance and static control specified separately
Request a Quote Browse Products

Novolac chemistry and static control address different duties

zhengfeng NOVOLAC-08 is a smooth conductive novolac epoxy flooring arrangement with a nominal 0.6–0.8 mm total build. It is intended for sound indoor floors where chemical handling and electrostatic control must be considered together. The construction includes compatible priming, a conductive underlayer, grounding and the specified novolac wearing formulation.

Novolac epoxy chemistry can support a more highly crosslinked resin network for selected chemical exposures. Conductivity requires a deliberately formulated electrical path through the wearing material and its connected layers. An ordinary novolac coating is not automatically an ESD coating, and a conductive epoxy is not automatically suitable for the process chemicals.

Define the exposure before selecting the resin

Identify each chemical or mixture, concentration, temperature and likely contact time. Intermittent splashes that are removed promptly impose a different duty from warm liquid standing overnight. Cleaning agents and repeated changes between hot and cold conditions belong in the assessment as well as the main process fluid.

Use resistance evidence for the actual supplied formulation and its cure state. Colour change, softening, loss of adhesion and loss of electrical function are different outcomes and need appropriate acceptance criteria. A broad chemical-resistant description cannot replace that assessment.

A thin coating is not automatically a containment lining

The nominal build leaves little capacity to conceal poor preparation or repair deep defects. Close pores and treat cracks before the conductive layer is installed, and preserve the required layer thickness instead of spreading material further over an unexpectedly rough base.

If liquid containment is required, specify drains, upstands, penetrations and movement joints as part of a documented assembly. A smooth nonporous field does not establish watertight connections or crack-bridging ability. A deeper lining or separate membrane may be needed where prolonged immersion, significant movement or severe impact governs the design.

Set the electrical requirements for the actual risk

For electronics work, define installed-floor measurements and the intended person, footwear and floor combination. Results for another proprietary coating or shoe cannot be assigned to this floor. The nominal thickness and the word conductive do not specify an acceptance resistance.

Where flammable vapours or combustible dusts may be present, the assessment must also address ignition hazards, process equipment and bonding. IEC TS 60079-32-1 provides guidance for that separate risk assessment. Electronics ESD criteria alone are not evidence of suitability for an explosive atmosphere.

Inspection, cleaning and repair

Include substrate preparation, the complete layer schedule, grounding points, chemical exposure data and agreed acceptance methods in the purchase scope. Inspect coating continuity before service and allow the selected material to reach the cure required for chemical contact.

After spills, remove contamination using a compatible procedure and inspect for damaged or softened areas. Residue and repair coatings can change the electrical surface even when the original floor remains visible. Restore affected layers with the approved system, then repeat the relevant electrical and continuity checks before returning the area to its intended duty.

Planning your Antistatic Epoxy Flooring Novolac Floor Coating specification?

Send us your dimensions, installation conditions, performance targets and required surface finish.

Talk to Our Team