A painted aluminium facing clips over a fixed backing angle to complete planned modular-room junctions.
  • 6063 aluminum components
  • 50 mm curved face
  • 3000 mm straight lengths
Request a Quote Browse Products

A 50 mm metal cove coordinated with modular panels

This assembly uses a 6063 aluminium backing angle and curved facing with a nominal 50 mm radius. The backing is screwed into position and the facing clips onto it. Reference straight lengths are 3000 mm, with a polyester-painted surface selected to sit visually with the adjacent panels.

A panel colour name alone is not a complete finish specification. Compare cured samples for shade, gloss and texture under the room lighting, especially where corner accessories and long extrusions are finished by different processes.

Plan intersections before straight runs

The backing angle establishes the attachment line and keeps the visible face clear of primary fixings. Its alignment determines whether both face edges sit consistently against the room surfaces. Correct irregular junctions before installing the angle; a cover should not be forced to bridge a large unsupported gap.

Three-way internal caps and fabricated or welded external corner pieces resolve different junctions. A three-way intersection joins three curved runs, while an external return changes direction around a projection. Select these pieces from the actual room geometry, with matching profile engagement and finished edge positions.

Sealing and service access

Seal the two contact edges with a product compatible with the paint and panel finish. Butt joints and corner interfaces also need an agreed detail. The mechanical clip provides retention, while the seals prevent the edges becoming collection points for cleaning residue.

Coordinate the cove with any demountable wall panels or service access. A clipped facing does not by itself guarantee that panels can be removed with the cove left in place. Show the intended removal sequence and which seals must be renewed after access. Where the cove meets the floor, account for floor movement and the selected wet-cleaning construction.

Supply scope and acceptance

Specify the aluminium grade, section, nominal radius, straight lengths, colour sample and counts of internal caps, external pieces and ends. Price backing, fixings, factory or site cuts, sealing and access requirements as part of the installed assembly.

At handover, inspect face alignment, firm attachment, edge continuity and finish consistency. Clean with products suited to the coating and sealant, and repair damaged seals before liquid or soil enters behind the facing. Metal construction and a rounded face do not establish a chemical-resistance, fire or cleanroom classification for the finished room.