Aluminum Air Duct 300 x 200 mm 0.8 mm
- Compact rectangular proportions suit crowded ceiling routes.
- Aluminum shell reduces material weight relative to a comparable steel section.
Route a compact dry-air branch in aluminum
The 300 × 200 mm section uses nominal 0.8 mm 3003-H14 aluminum sheet for a lightweight rectangular air passage. Its Pittsburgh lockseam and transverse flange arrangement suit fabricated modular ductwork. The shallow profile can help route a small branch through limited ceiling space, but the shell still requires a defined pressure and support design.
Low mass does not mean steel-equivalent stiffness
Aluminum reduces material mass for comparable geometry, while its stiffness differs from steel. Do not copy a steel thickness or flange detail without checking the aluminum construction. For this compact section, sheet thickness, section length, transverse joints and support spacing work together to control deformation. A nominal 0.8 mm designation is not a pressure rating.
| Product reference | Drawing requirement |
|---|---|
| 300 × 200 mm internal passage | Finished dimensions and the outside envelope after flanges and insulation. |
| 3003-H14, nominal 0.8 mm | Material and thickness tolerances, fabrication condition and permitted service. |
| Pittsburgh seam; TDC-style ends | Approved seam closure, flange profile, corners, clamps and compatible gaskets. |
| Single wall, mill finish | Separate thermal insulation and vapour-barrier requirements where needed. |
A folded seam creates a mechanical joint; it does not by itself establish an airtight class. Sealant selection and application must suit the metal, air stream and required leakage performance. A TDC-style description also does not guarantee that another manufacturer's flange components will mate.
Install without damaging the thin shell
Support the duct across suitable bearing surfaces and avoid overtightened fasteners that distort flanges. Keep loads from equipment or service personnel off the duct. At mixed-metal connections, consider moisture and galvanic compatibility when selecting fasteners and isolating details.
Aluminum conducts heat readily; single-wall metal is not insulation. Cold-air branches may need continuous exterior insulation and vapour sealing at joints and supports. Keep the inside clean during construction and use cleaning materials compatible with aluminum, rather than assuming a stainless cleaning process is suitable.
Quotation and acceptance
Provide flow, pressure, route, section lengths and environmental conditions. Quote joints, sealant, supports, fittings and insulation scope explicitly. Inspect alloy/thickness records, dimensions, seam engagement and damage, then perform the agreed leakage test on the defined installed section. Dry-air selection does not establish suitability for corrosive, wet or fire-rated exhaust service.
Planning your Aluminum Air Duct 300 x 200 mm 0.8 mm specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.