Airtight Shut-Off Damper 800 x 755 mm Pneumatic Gas-Tight
- Pneumatic drive suits systems with an instrument-air supply.
- A larger near-square opening accommodates medium critical branches.
Operate an isolation linkage from an instrument-air system
The 800 × 755 mm pneumatic assembly uses a double-acting cylinder to move the sealing blades through an over-centre mechanism. Compressed air supplies the opening and closing strokes. At the fully achieved locked position, the linkage can mechanically retain the intended seal compression; reaching that position is a separate functional requirement.
Loss of air does not automatically produce closure
A double-acting cylinder does not inherently drive closed when its supply disappears. If air is lost during travel, the mechanism may not reach its locked end state. Define behaviour for loss of instrument air, loss of solenoid power, a blocked exhaust and a missing close command. Any stored-energy or backup provision must be explicitly designed and supplied rather than assumed from the mechanical lock.
| Reference | Information needed |
|---|---|
| 800 × 755 mm welded coated frame | Connection details, support and permitted pressure in each direction. |
| Double-acting cylinder | Working pressure range, force through the linkage, air consumption and travel time. |
| Filtered compressed air | Required particle, water and oil quality for the chosen pneumatic components. |
| Optional solenoid and end sensing | Valve function, coil supply, exhaust arrangement, switch logic and wiring. |
A nominal 6 bar supply is not enough information: pressure at the cylinder can fall during operation through undersized lines or other users' demand. Cylinder force must be adequate against the actual duct pressure and seal resistance throughout the stroke.
Make the leakage requirement measurable
The gas-tight title states an intended duty. Specify permissible blade and casing leakage, test pressure, direction and method for this supplied assembly. Leakage and pressure ratings must be supported by testing applicable to the supplied configuration. A closed-position signal does not detect damaged seals or flange leakage.
Install the frame square, protect pneumatic tubes and leave access to the cylinder, linkage and neoprene sealing surfaces. Inspect condensate management, tubing damage, seal condition and actual end-state movement. Isolate stored pneumatic energy before servicing the mechanism.
Quotation and functional tests
Include air preparation, solenoid, tubing interfaces, switches and required backup functions in the scope. Acceptance should test opening and closing at the minimum specified air supply and worst duct duty, the agreed failure sequences, position indication and documented leakage performance.
Planning your Airtight Shut-Off Damper 800 x 755 mm Pneumatic Gas-Tight specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.