Airtight Shut-Off Damper 400 x 270 mm Manual Gas-Tight
- Positive mechanical closure is retained after the operator releases the wheel.
- The shallow rectangular opening suits small containment branches.
Manually close a branch against a dedicated sealing frame
The 400 × 270 mm handwheel assembly moves its blades against a seal through an over-centre linkage. Once the linkage reaches its designed locked position, the geometry retains seal compression without a continuously powered drive. This differs from a balancing quadrant that merely fixes an intermediate blade angle.
Specify what the required gas-tight duty means
The product name identifies the intended isolation duty, not a verified zero-leakage result. Establish an allowable leakage, test gas, pressure difference, pressure direction and test method for the actual assembly. Leakage through closed blades, through the casing and around site flanges are different paths. A low value from another manufacturer's damper does not establish any of them here.
| Reference construction | Selection detail |
|---|---|
| 400 × 270 mm nominal opening | Actual clear passage, flange drilling and space to operate the handwheel. |
| Welded casing; 3 mm reference thickness | Approved fabrication, structural pressure duty and connection loading. |
| Neoprene foam sealing frame | Compatibility with the air, cleaning chemicals, temperature and compression cycle. |
| RAL 7001 coated finish | Surface specification and protection of the seal and moving parts during finishing. |
The pressure that a closed assembly can withstand is not necessarily the pressure against which it can be opened or closed. Pressure helping seat a blade is also different from reverse pressure tending to unseat it. Define both operating directions and the required manual effort.
Retain the seal without damaging it
Mount the frame without twist and use compatible flange gaskets. Provide access to inspect the sealing line and linkage. The handwheel reaching a stop is not a leakage measurement; debris or a damaged gasket can prevent effective sealing even when the mechanism appears closed. Do not use extensions to force a binding drive.
Inspect compression damage, adhesion, contamination and linkage wear during the maintenance interval. Replacement seals must match the approved material and geometry. Recheck closure after repairs and follow the site's isolation procedure before opening the duct.
Quotation and acceptance
Quote the handwheel damper, connection details, optional limit switches, seal specification and required leakage testing. Agree the acceptance pressure, direction and permissible leakage before purchase. An end switch confirms a position only; it does not establish containment, fire resistance or nuclear qualification.