Airtight Shut-Off Damper 1000 x 1000 mm Electric Gas-Tight

A large geared-drive isolation assembly needs explicit end-state, power-loss and sealing acceptance requirements.
  • Large square face suits main containment routes.
  • Electric drive supports integration with shutdown controls.
Request a Quote Browse Products

Close a large isolation damper with a geared electric drive

The 1000 × 1000 mm assembly couples a geared motor to blades that seat against a dedicated sealing frame through an over-centre linkage. Remote operation is useful on a main ventilation route. The drive must complete the seating movement, after which the designed mechanical lock retains the closing geometry.

Specify power failure at every stage of operation

Retaining an already closed mechanism is different from moving an open damper closed during a power failure. A standard geared electric drive does not supply that missing energy. Define the required state on power loss, whether travel must finish, and any backup power or independent energy storage. The shutdown sequence must also coordinate fans and other dampers so that pressure loads remain within the verified duty.

Reference configurationInterface requirement
1000 × 1000 mm frame; 3 mm reference casingApproved fabrication, weight, support locations, flange arrangement and pressure directions.
230 V single-phase or 400 V three-phase AC, 50 Hz optionsSelect one motor version with matching protection, control circuit and wiring.
Neoprene foam seal and RAL 7001 finishMaterial compatibility, seal replacement method and environmental limits.
Optional open/closed switchesActual blade-end indication, contact rating and alarm logic.

For three-phase equipment, correct rotation and travel limits need verification during commissioning. Stops, torque protection and end switches must be set according to the selected drive and damper instructions. An indicated closed position cannot by itself verify leakage or prove that every blade is seated.

Preserve sealing geometry on a large frame

Support the weight independently and align the duct flanges without pulling the casing out of square. Leave room to remove the drive and reach the full sealing perimeter. Inspection should cover unequal blade travel, debris on seals, compression damage and linkage wear; a stronger motor is not a remedy for distorted mounting.

Define gas-tight acceptance before ordering

The name describes the intended duty. Agree allowable blade and casing leakage, test pressure, direction and method for the actual assembly. Do not use another manufacturer's numerical leakage or closing-pressure claims as this product's rating.

Quote the motor version, controls, limit switches, connection gaskets, backup function if needed and leakage-test documentation. Handover should demonstrate loaded operation, shutdown interlocks and power-loss behaviour as well as the specified leakage result. Fire, smoke or nuclear qualification requires separate evidence.