Adjustable Louver Air Grille 300 x 150 mm Single-Deflection
- One blade bank offers direct access for setting.
- Airfoil sections provide a smooth directional passage.
Single-plane direction control for a small supply opening
The 300 × 150 mm single-deflection grille uses one bank of individually adjustable blades to steer supply air. It is useful for a small wall or exposed-duct outlet where the required adjustment is mainly in one plane. The blade orientation must be selected with the mounting position: blades parallel to the long dimension steer in a different plane from blades parallel to the short dimension.
Direction and volume are separate adjustments
Turning the blades changes the discharge direction and also influences resistance, spread and throw. It is not a calibrated method of setting air quantity. An optional rear opposed-blade damper can provide balancing, while the face blades are set for the desired distribution. Damper access and clearance must be included in the installation layout.
If both vertical and horizontal steering are needed, a double-deflection arrangement provides two perpendicular blade banks. The required size still needs to be selected separately; a larger nominal face is not automatically suitable for the same branch duty.
Reference construction
| Item | Selection detail |
|---|---|
| Nominal size | 300 × 150 mm; coordinate the actual neck, border and opening dimensions. |
| Blade arrangement | Single bank of adjustable extruded-aluminum airfoil blades. |
| Reference blade pitch | 19.05 mm, equivalent to 3/4 in, subject to the selected construction. |
| Finish | White or another specified finish with suitable cleaning compatibility. |
| Balancing option | Rear opposed-blade damper, specified with material and access method. |
Select for the occupied space
Supply temperature, mounting height, airflow and blade angle all influence the air pattern. A jet directed away from one workstation may strike another obstruction or return too quickly to an extract grille. Use performance data for the actual size and settings, then check the room arrangement during commissioning.
A smooth approach from the duct or plenum helps avoid local noise and uneven discharge. Leave access for cleaning without bending the blades or losing their settings. The grille is an air-distribution component, not a terminal HEPA filter or a process-containment device.
Specify design flow, available pressure, required throw, sound criterion, blade orientation, border, fixing and damper in the quotation. Handover should record the balanced flow and final blade positions so maintenance can restore the intended distribution.
Planning your Adjustable Louver Air Grille 300 x 150 mm Single-Deflection specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.