Adjustable Disc Air Valve DN100 Exhaust
- Small 130 mm face limits the visible footprint.
- Threaded disc offers gradual opening adjustment.
Manual trimming at a small circular extract point
The DN100 disc valve terminates a small extract branch with a round room-side face and adjustable central disc. Rotating the threaded disc moves it axially, changing the annular passage through which room air enters the duct. It provides local manual balancing for suitable general support-room ventilation.
A disc position is not an airflow setting by itself
Flow depends on both the opening and the pressure available at the valve. The same number of turns can produce different quantities on branches with different resistance. Adjust while measuring with the method specified for the selected valve, then record the final opening and measured flow. A pressure-based method needs the correct coefficient for the actual valve and setting.
Closing the disc excessively can create a narrow, noisy passage. If a branch requires severe throttling, review its upstream balance and terminal selection instead of relying on a nearly closed face. The valve is not an automatic constant-flow regulator or a gas-tight isolation device.
Reference construction and interfaces
| Item | Specification basis |
|---|---|
| Connection | DN100 nominal circular duct. |
| Visible face | 130 mm reference outside diameter. |
| Body | Painted galvanized sheet metal, white finish referenced to RAL 9010. |
| Attachment | Matching bayonet mounting socket and its specified sealing arrangement. |
| Position | Wall or ceiling installation within the supplied mounting instructions. |
The duct size, socket engagement and finished opening are separate details. Secure the socket to a suitable support and seal around it so air does not bypass into the ceiling void. A compatible-looking ring is not sufficient evidence that the bayonet parts will lock together.
Cleaning without losing the balance
Deposits around the annulus reduce the passage. Record the disc position before removal and use the approved body-release method, avoiding unintended rotation of the adjusting disc. Clean compatible surfaces, refit securely and check that the original setting has been restored.
Specify flow, pressure, sound criterion, socket, finish and maintenance access in the quotation. Acceptance should include the installed extract quantity and secure mounting. A general extract valve does not provide capture of hazardous laboratory fumes or terminal cleanroom filtration; those duties need an appropriate dedicated system.
Planning your Adjustable Disc Air Valve DN100 Exhaust specification?
Send us your dimensions, installation conditions, performance targets and required surface finish.