Dedicated fresh-air path
The make-up connection introduces controlled outside supply without replacing the local recirculation loop.
This RCU adds documented make-up and exhaust connections to a 1000 m³/h nominal local recirculation path. Up to 500 m³/h of make-up air can be introduced while an H14 filter protects the supply, and Modbus RTU provides control-system communication. The model is intended for positive-pressure rooms that need both local circulation and a measured fresh-air path.
The make-up connection introduces controlled outside supply without replacing the local recirculation loop.
Make-up and exhaust connections allow the room airflow balance to be coordinated around a pressure target.
Modbus RTU supports connection to a supervisory cleanroom control system.
| Nominal Recirculation Airflow | 1000 m³/h |
|---|---|
| Maximum Make-Up Airflow | 500 m³/h |
| Final Filter | H14 |
| Communication | Modbus RTU |
| Air Connections | Dedicated make-up and exhaust interfaces |
| Operating Mode | Local recirculation with controlled fresh air |
| Pressure Strategy | Positive-pressure room supply |
| Kawalan Aliran udara | Recirculation and make-up duties balanced together |
| Installation | Cleanroom ceiling or technical plenum |
| Penyesuaian | Boleh didapati berdasarkan aplikasi yang dimaksudkan dan persekitaran operasi. |
Recommended for positive-pressure pharmaceutical and precision-production rooms that need local filtered recirculation plus controlled fresh air. Exhaust and leakage must be included in the final mass balance.
Define make-up and exhaust connection sizes, H14 seal, Modbus addressing and access arrangement. Final flows should be set from the room pressure cascade.
Hantarkan kepada kami dimensi anda, syarat pemasangan, sasaran prestasi dan kemasan permukaan yang diperlukan.