클린룸 장비 및 무균 시설 필수품의 원스톱 공급업체국제 프로젝트 지원
Open mobile navigationClose mobile navigation
/ 제품 / Cleanroom Air Filters / Photocatalytic Oxidation Filter Module 10 W 1500 m3/h
STJH-PCO-MODULE-10W-1500

Photocatalytic Oxidation Filter Module 10 W 1500 m3/h

The shortest PCO module in the series for small ducts and air-conditioning equipment up to 1500 m3/h.
  • Up to 1500 m3/h
  • 10 W compact module
  • 227 mm treatment section
견적 요청 제품 찾아보기

상품 소개

A 227 mm treatment section and 10 W electrical load make this the compact member of the PCO family. UV-C energy activates the TiO2 photocatalytic surface as air passes through the duct-mounted assembly. The unit includes an airflow sensor, lamp-life display and alarm or control connections, allowing its operating state to be supervised instead of treating the lamp as an unmonitored component. Selection still requires review of pollutant type, exposure time and upstream particle control.

주요 기능

Compact duct insertion

The shortest treatment section suits smaller air-conditioning branches and packaged equipment.

Monitored lamp operation

Airflow sensing, service-life indication and alarm connections make lamp status visible to maintenance staff.

Photocatalytic treatment

UV-C activates a TiO2 surface to treat selected organic pollutants in the passing air stream.

기술 매개변수

Electrical Power10 W
Supply220-240 V, 50/60 Hz
Rated Current0.05 A
Overall Dimensions250 x 157 x 299 mm
Treatment Section Length227 mm
Maximum Airflow1500 m3/h
Ingress ProtectionIP20
Treatment MethodUV-C activated TiO2 photocatalysis
ControlsAirflow sensor, lamp-life display, alarm and control ports
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

Applications

For small ducted air-conditioning units, cleanroom support-air branches and local recirculation equipment requiring compact treatment of selected organic contaminants.

Solutions for Your Application

The module is applied at an airflow higher than its treatment section can support.Keep branch flow at or below 1500 m3/h and provide parallel modules when the duct duty is greater.
Lamp output declines without a visible maintenance warning.Connect the lamp-life and alarm outputs to the local control routine and replace components on the validated schedule.

사용 가능한 옵션

Confirm duct airflow, pollutant profile, insertion location, service access, electrical isolation, alarm interface and upstream particle filtration.

Planning a Photocatalytic Oxidation Filter Module 10 W 1500 m3/h specification?

치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.

우리 팀과 대화하십시오.
저희에게 이메일 whatsapp WeChat