STJH-MULTI-STAGE-HOUSING-PRE-HEPA

Multi-Stage Air Filter Housing Two-Stage Prefilter and HEPA

A matched two-stage cabinet that protects the final HEPA with a serviceable upstream coarse filter.
  • Coarse prefilter plus HEPA
  • 2, 4 or 6 in prefilter depths
  • Side-access welded cabinet
견적 요청 제품 찾아보기

상품 소개

This two-stage assembly combines a 2, 4 or 6 in prefilter track with a downstream full-depth HEPA section. The coarse stage captures larger dust before it loads the expensive final element, reducing premature HEPA resistance and extending useful service. A fully welded side-access cabinet keeps both filters in one coordinated pressure boundary while allowing each stage to follow a different replacement trigger.

주요 기능

HEPA life protection

The first stage removes coarse loading before it reaches the high-efficiency final filter.

Selectable prefilter depth

Two-, four- and six-inch tracks support different capacity and resistance targets.

Integrated service section

Matched doors and filter tracks keep both stages accessible within one modular housing train.

기술 매개변수

Number of Stages2
First StageCoarse particle prefilter
Prefilter Depth2, 4 or 6 in
Final Stage12 in class HEPA filter
Housing ConstructionFully welded metal
AccessSide access
Filter SealsMatched gasket compression tracks
Primary PurposeExtend final HEPA service life
InstallationSupply or recirculation AHU
사용자 정의의도된 응용 프로그램 및 운영 환경에 따라 사용할 수 있습니다.

Applications

For medical and clean-manufacturing air handlers that need dependable final HEPA filtration and a replaceable dust-loading stage upstream.

Solutions for Your Application

Both filters are replaced together even though only the prefilter is loaded.Monitor stage pressure separately and change each element according to its own resistance or integrity criterion.
A high-resistance prefilter consumes too much of the fan allowance.Choose the prefilter depth and efficiency from dust load, service interval and available total static rather than capacity alone.

사용 가능한 옵션

Confirm prefilter grade and depth, HEPA size, cabinet material, access side, individual pressure taps, test ports and duct connections.

Planning a Multi-Stage Air Filter Housing Two-Stage Prefilter and HEPA specification?

치수, 설치 조건, 성능 목표 및 필요한 표면 마감을 보내십시오.