천장 장착 공기 처리 장치 (ceiling mounted air handling unit)
- Low-Profile Casing
- Bottom Service Access
- Direct-Drive Fan
- Condensate-Safe Installation
상품 소개
The ceiling-mounted air handling unit condenses the required filter, coil, drain pan and fan functions into a shallow casing suspended above a corridor or support area. Hinged or removable lower panels provide service access without requiring side clearance. A direct-drive fan avoids belt maintenance in the restricted ceiling void, while a full-width drain pan and correctly trapped outlet protect the ceiling below. Flexible connections and vibration isolators limit structure-borne noise.
주요 기능
Bottom-access filters and fan assemblies can be serviced from a defined ceiling hatch.
A full-width sloped drain pan controls condensate beneath the cooling coil.
Direct-drive EC or plug fans provide airflow turndown without belt adjustment overhead.
응용 프로그램 솔루션
Ceiling equipment must remain shallow, drain reliably and permit maintenance from below without contaminating the occupied space.
일반적인 응용 프로그램
기술 매개변수
Representative construction ranges for a low-profile ceiling air handler are shown below.
| 핵심 재료 | Closed-cell polyurethane or mineral-wool acoustic insulation within double-skin casing |
|---|---|
| 패널 두께 | 25–50 mm insulated low-profile panel |
| 유효 폭 | 700–2200 mm nominal casing width |
| 최대 길이 | Up to 5000 mm overall suspended length |
| 강철 면면 두께 | 0.5–0.75 mm galvanized or coated sheet skins |
| 코어 밀도 | 38–44 kg/m³ polyurethane or 64–90 kg/m³ mineral wool |
| 열전도도 (Thermal Conductivity) | 0.023–0.040 W/(m·K) according to insulation |
| 표면 마무리 | Powder-coated galvanized outer casing with smooth galvanized inner liner |
| 접합 유형 | Gasketed folded-panel joints with bottom-access doors and flexible duct collars |