Compact instantaneous package
The skid heats flow on demand without a large local storage vessel.
This compact package is documented for 40 gpm hot-water delivery using 100 gpm on the boiler-water side and a 6 gpm recirculation circuit. A single- or double-wall exchanger can be selected to separate the heating loop from the delivered water. Factory packaging combines the exchanger, controls and circulation components for small clean facilities where field-built hot-water stations would add coordination time.
The skid heats flow on demand without a large local storage vessel.
A heat exchanger isolates boiler water from the clean-side distribution circuit.
The 6 gpm return circuit maintains temperature at remote use points during low draw.
| Hot-Water Flow | 40 gpm |
|---|---|
| Boiler-Water Flow | 100 gpm |
| Recirculation Flow | 6 gpm |
| Heat Exchanger | Single or double wall |
| Package Type | Water-to-water instantaneous heater |
| Temperature Control | Electronic packaged control |
| Pumps | Matched primary and recirculation duties |
| Connections | Sized to selected flow and piping code |
| Primary Scale | Small facility hot-water station |
| Customisierung | Verfügbar je nach beabsichtigter Anwendung und Betriebsumgebung. |
For small clean-facility wash points, equipment hot water and controlled process or sanitation distribution.
Specify supply temperature, exchanger wall type, boiler conditions, pumps, recirculation setpoint, materials, valves and controls.
Senden Sie uns Ihre Abmessungen, Installationsbedingungen, Leistungsziele und gewünschte Oberflächenveredelung.