Laman Utama / Produk / Peralatan Bilik Bersih / Integrated HEPA Clean Air Supply Module
FFU dan Peralatan Penulenan Udara Terminal

Modul Bekalan Udara Bersih HEPA Bersepadu

A coordinated ducted supply terminal bringing the plenum, final filter, balancing arrangement and room-side diffuser into one ceiling assembly.
  • Coordinated Terminal Package
  • Duct-Supplied Operation
  • Accessible Balancing Options
  • Matched Filter and Diffuser
Permintaan sebut harga Semak imbas produk

Pengenalan Produk

The integrated HEPA clean air supply module is specified as a complete ceiling terminal rather than a bare filter casing. Its duct inlet, distribution plenum, final-filter seat and room-side front plate form a matched air path. A selected balancing arrangement and test connections make the terminal easier to operate after the ceiling is closed. Conditioned air comes from the central system; the module does not contain its own circulation fan.

Ciri-ciri Utama

Matched terminal components reduce uncertainty at the filter-to-diffuser interface.

Room-side balancing access can avoid entering a crowded ceiling void.

Separate pressure and aerosol connections support different checks without confusing their functions.

Front-plate selection adapts the air-distribution pattern to the intended room layout.

Penyelesaian untuk permohonan anda

A coordinated supply point helps avoid mismatches between installation, balancing and maintenance needs.

A front plate conflicts with the filter retaining hardware.Select the diffuser and retention mechanism as part of the terminal assembly rather than purchasing the visible face separately.
Supply volume needs adjustment after services fill the ceiling void.Choose room-side access to the balancing mechanism and verify its reachable position on the fitted terminal.
Routine checks require repeated access above the room.Arrange the selected pressure and aerosol connections at accessible locations and identify each connection clearly.
A revised room layout changes the desired discharge pattern.Review a compatible perforated, radial or swirl face together with the room's supply and return positions.

Permohonan yang biasa

Suite pengeluaran farmaseutikalHospital clean treatment roomsBiotechnology laboratoriesMedical-device assembly areasDucted microelectronics cleanrooms

Parameter teknikal

Common reference configuration choices for the ducted terminal, balancing arrangement and final-filter assembly.

Operating ArrangementCentrally supplied ducted terminal without an integral fan
Common Panel Face Options610 x 610 mm or 915 x 610 mm nominal final-filter dimensions
Common Round Inlet Options200 mm, 250 mm or 315 mm nominal duct diameter
Common Filter Frame Depth78 mm for a flat-seal configuration; deeper filter arrangements available
Common Casing FinishesWhite powder-coated steel or stainless steel
Balancing ArrangementInlet volume-control damper; room-side adjustment option
Filter-Retention InterfaceCompression-seal frame or compatible gel-seal configuration
Testing ConnectionsUpstream pressure and aerosol connections as selected
Air-Distribution OptionsPerforated, radial or swirl front plate matched to the terminal
PenyesuaianBoleh didapati berdasarkan aplikasi yang dimaksudkan dan persekitaran operasi.

Pilihan yang boleh didapati

Top or side supply connectionManual or room-side damper adjustmentMatched HEPA or ULPA filter assemblyPerforated, radial or swirl front plate

Filter, damper, test fittings and diffuser inclusion are selected as part of the quoted package; a different option may require a different terminal body.

Selection and Installation

Choose a complete terminal arrangement

Define the required inlet position, ceiling interface, filter size and class, damper access and diffuser pattern together. The common panel dimensions are not the external terminal dimensions or the ceiling opening. Check that every selected component belongs to the same assembled configuration rather than combining unrelated catalogue parts.

Use the central supply system correctly

This is a duct-supplied terminal, unlike the fan-powered HEPA module. The central fan must overcome duct, damper and loaded-filter resistance at the required volume. A balancing damper trims flow; it cannot increase insufficient supply pressure or provide automatic constant-volume control by itself.

Keep test access usable after installation

Identify which connections are for pressure readings, aerosol introduction and upstream concentration sampling. Their functions are not interchangeable. Keep adjustment points and sampling connections reachable with the selected front plate fitted, and preserve enough space to replace the final filter without disturbing nearby terminals.

Balance the room, not only the outlet

Check the delivered volume and discharge pattern with the other supply and extract points operating. Diffuser choice affects mixing and local air direction, but does not establish room cleanliness, sterility or containment. Include the required room-level airflow assessment alongside final-filter integrity checks.